Installation & Servicing instructions ATAG iC-Range
43
Step 2: CO
2
check on low load
Set the low load
The low load of the boiler can be set by you as follows:
- Press on the - button until the minimum value (0%) has been reached (low load)
- Use the measuring tool to carry out a CO
2
control measurement. The detected values must lie in the
measuring range shown below.
The CO
2
value at low load must be lower than the CO
2
value at full load. The measuring procedure must
be carried out, until a constant measuring result is achieved. Please contact ATAG, if the values should lie
outside of the applicable tolerances.
End of measuring:
- Press the ESC button (
button).
The device switches off .
The display shows for 2 seconds code 180 or 181.
This completes the procedure.
The maximum duration of the commissioning function, without interruption, is 8 minutes.
Measuring point CO
2
Figure 15.1.a
a
CO
2
check on low load (Step 2)
Low load
Natural gas (G20)
Propane (G31)*
CO
2
Example readings
Full load recorded
Accepted low range
Full load recorded
Accepted low range
9.6%
9.3% - 7.5%
11.0%
10.9% - 8.9%
9.5%
9.2% - 7.5%
10.9%
10.8% - 8.9%
9.4%
9.1% - 7.5%
10.8%
10.7% - 8.9%
9.3%
9.0% - 7.5%
10.7%
10.6% - 8.9%
9.2%
8.9% - 7.5%
10.6%
10.5% - 8.9%
9.1%
8.8% - 7.5%
10.5%
10.4% - 8.9%
9.0%
8.7% - 7.5%
10.4%
10.3% - 8.9%
8.9%
8.6% - 7.5%
10.3%
10.2% - 8.9%
8.8%
8.5% - 7.5%
10.2%
10.1% - 8.9%
8.7%
8.4% - 7.5%
10.1%
10.0% - 8.9%
8.6%
8.3% - 7.5%
10.0%
9.9% - 8.9%
9.9%
9.8% - 8.9%
Values are valid with closed cover/air box.
* Only possible if LPG conversion kit is installed!
Содержание iC 24
Страница 33: ...Installation Servicing instructions ATAG iC Range 33 Figure 10 7 a 10 9 Electrical diagram...
Страница 56: ...Installation Servicing instructions ATAG iC Range 56 Annex C Short parts list...
Страница 57: ...Installation Servicing instructions ATAG iC Range 57...
Страница 58: ......
Страница 59: ......
Страница 60: ......
Страница 61: ......