58
EN
Maintenance
Warning!
Danger due to faulty or improperly performed maintenance:
The owner is
responsible for correct installation and functional inspection of the product and
connected components.
· The safe function must be tested by a trained qualified exp
at least once per
year
.
· Requirements established by inspection authorities must be complied with,
ASSA ABLOY Sicherheitstechnik GmbH
offers training for qualification in the requi-
site skills.
Observe the following in particular:
· A test log must be created at the time of the initial commissioning, wherein a
description of the installed escape route securing system, configuration param-
eters, and results of the complete functional testing are recorded ("Test log for
commissioning," page 60).
· All further maintenance must be recorded in a suitable test log book (available
from ASSA ABLOY Sicherheitstechnik GmbH).
· If permissible and officially approved modifications of the escape route securing
system should take place at a later time, they must be recorded in the same
manner as for an initial commissioning.
· Ensure that all opening and closing functions of the escape door function with-
out limitation when the escape route securing system is deactivated.
· Ensure that the escape door is secured after activation of the escape route
securing system.
· Ensure that the escape door can be opened after the Emergency Open
buttons(s) is (are) pressed.
· Ensure that the escape door is unlocked on actuation by a connected fire alarm
system.
· All components of the escape route securing system must be inspected for
damage, changes, and secure mounting and the configuration and safe func-
tionality must be assured.
· It must be ensured that there are no relevant deviations from the recorded
initial commissioning with respect to condition, configuration, and functional-
ity. If there are deviations, they must be recorded accordingly and subjected to
approval by inspection authorities.
!
At the time of the
initial
commissioning
For each
scheduled
maintenance
Maintenance
Содержание ePED 1386-00
Страница 38: ...38 EN Fitting and installation ...
Страница 62: ...62 EN ...
Страница 63: ...63 EN ...