39
EN
Fitting and installation
Installation
Pre-requirements
Plan and install the wiring before the
ePED
®
1386-00 door terminal
has been
mounted (manual
D0102100 ePED
®
Hi-O Technology™ bus
).
Note!
Protection rating IP30 must be achieved:
Switch boxes (Fig. 28) which achieve a
minimum protection rating of IP30 must be used for the installation.
Attention!
Limitation of function with incorrect operating voltage at the components.
A
mains adapter in accordance with DIN EN 60950-1 SELV must be used. Separate mains
adapters must be connected for the supply of devices with power consumption higher
than 100 VA. The appropriate mains adapter, the cable lengths, and cable cross sections
must be chosen according to the local circumstances. Check and ensure that the oper-
ating voltage at the connection points is suitable for the components.
Identification of the cable
Note!
Choose uniform identification for avoidance of errors:
In order to avoid errors
and for a clearer overview during installation and maintenance,
ASSA ABLOY Sicher-
heitstechnik
recommends uniform identification and colour coding of the cable
cores Tab. 4.
Function
Screw
terminal
Colours
Typical
CAN bus
Hi-O
J-Y(ST)Y 4x2
Hi-O
CAN_H
1
wh
wh/br
CAN_L
2
br
br
V
B
+
3
gn
gn
GND
4
ye
wh/gn
I
I
Tab. 4 :
Colour coding for
wiring
Fitting and installation
Содержание ePED 1386-00
Страница 38: ...38 EN Fitting and installation ...
Страница 62: ...62 EN ...
Страница 63: ...63 EN ...