18
EN
Functions
Fire alarm
In the case of a fire alarm, the
Hi-O Technology
™ components are actuated by a
fire alarm system. The escape route locking systems are automatically unlocked
and retain this status until actuation by the fire alarm system is lifted again.
If the actuation by the fire alarm system is lifted again, the components lock again
if no further release commands are issued.
Other
Hi-O Technology™
locking systems respond according to their respective
configuration.
Emergency unlocking
If the Emergency Open push-button is pressed, an Emergency unlocking or re-
lease request is issued to the central control. If an Emergency unlock has been
triggered with an Emergency Open push-button, the Emergency Open push-
button must be unlocked manually, wherein the system is also reset to normal
operation.
Tamper message/fault message
The following statuses trigger a tamper message for a locked door:
· The door is open and/or
· the escape route locking system is unlocked.
The door remains in Locked status.
The
tamper
status can be reset centrally or at the door.
Message
Intrusion alarm system activated
If a block command is issued by an intrusion alarm system, lock commands are
transmitted to all
Hi-O Technology
™ component and all control devices are
deactivated.
The escape door can only be opened after the Emergency Open push-button has
been pressed.
The following commands are exceptions and can still be activated:
· Resetting of Emergency unlock,
· Activation of escape route locking systems ("Active and inactive escape route
securing system," page 17).
gn
gn
gn
gn
ye
ye
ye
ye
Fire alarm
and/or Emergency
unlocking
rd
rd
rd
rd ye
ye
ye
ye
Tamper alarm has
Locked
status
rd
rd
rd
rd
Intrusion alarm
system is active