background image

Operation

WARNING: Never shut down this unit by unplug-

ging it from the power source.

ef

fi

 ciency of your stove. Providing correct combustion air will 

reduce the frequency of cleaning your glass door and prevent 
the rapid buildup of creosote inside your stove and chimney.

You should adjust the damper based on the fire’s 

appearance. A low, reddish, dirty 

fi

 re can be improved by 

turning the dampener slightly to the right. A “blow torch” 

fi

 re 

can be improved by turning the dampener to the left a little bit.

As a general rule, on lower feed rate settings, the damper 

should be farther to the left closing it off. On higher feed 
rates, the damper should be open more by having it set more 
towards the right. Through trial and error, you will 

fi

 nd the best 

setting. Consult your dealer if you need help.

NOTE: On heat range “1”, damper should be either 

completely closed or open no more than a ¼ of the way. If 
damper is open to far, it can cause the 

fi

 re to go out.

OPENING DOOR

If the door is opened while the stove is in operation it must 

be closed within 30 seconds or the stove will shut down. If 
the stove shuts down push the “On/Off” button to re-start 
your stove. The stove will have to fully shut down and turn 
off before you will be able to restart the stove.

ROOM AIR FAN

When starting your stove the Room Air Fan will not come 

on until the stove’s heat exchanger warms up. This usually 
takes about 10 minutes from start-up.

IF STOVE RUNS OUT OF PELLETS

The 

fi

 re goes out and the auger motor and blowers will 

run until the stove cools. This will take 30 minutes or longer 
depending on the heat remaining in the appliance. After the 
stove components stop running all lights on the display will 
go out and the two digit display will begin 

fl

 ashing “E3”

REFUELING

• 

The hopper and stove top will be hot during operation; 
therefore, you should always use some type of hand 
protection when refueling your stove.

• 

Never place your hand near the auger while the stove 
is in operation.

We recommend that you not let the hopper drop below ¼ full.

KEEP HOPPER LID CLOSED AT ALL TIMES EXCEPT 

WHEN REFILLING. DO NOT OVERFILL HOPPER.

SHUTDOWN PROCEDURE

Turning your stove off is a matter of pressing the “POWER” 

button on the display board. The green light will turn back to red 
when the “POWER” button is pushed. The auger motor will stop, 
and the blowers will continue to operate until the internal 

fi

 rebox 

temperatures have fallen to a preset level.

1.  Your stove is equipped with a high temperature thermodisc. 

This unit has a manual reset thermodisc.  This safety 
switch has two functions.

A.  To recognize an overheat situation in the stove 

and shut down the fuel feed or auger system.

B.  In case of a malfunctioning convection blower, the 

high-temperature thermodisc will automatically 
shut down the auger, preventing the stove from 
overheating.

NOTE: On some units, once tripped, like a circuit breaker, 

the reset button will have to be pushed before restarting your 
stove. On other units the thermodisc has no reset button and 
will reset itself once the stove has cooled. The manufacturer 
recommends that you call your dealer if this occurs as this 
may indicate a more serious problem. A service call may be 
required.
2.  If the combustion blower fails, an air pressure switch will 

automatically shut down the auger.

NOTE: Opening the stove door for more than 30 seconds 

during operation will cause enough pressure change to 
activate the air switch, shutting the fuel feed off.  The stove 
will shut down and show “E2” on the two digit display. The 
stove has to fully shut down before restarting.

TAMPER WARNING 

This wood heater has a manufacturer-set minimum low burn 

rate that must not be altered. It is against federal regulations 
to alter this setting or otherwise operate this wood heater in a 
manner inconsistent with operating instructions in this manual.

VISIBLE SMOKE

The amount of visible smoke being produced can be an 

effective method of determining how ef

fi

 ciently the combustion 

process is taking place at the given settings. Visible smoke 
consist of unburned fuel and moisture leaving your stove. 
Learn to adjust the air settings of your speci

fi

 c unit to produce 

the smallest amount of visible smoke. Wood that has not been 
seasoned properly and has a high wood moisture content will 
produce excess visible smoke and burn poorly.

20

Содержание Ashley AP5660

Страница 1: ...e Contact your local building or fire officials about restrictions and installation inspection requirements in your area These Pellet Stove Room Heaters have been designed for use in the US and Canada and are suitable for mobile homes The French version of this manual is available for download at www usstove com Save These Instructions United States Stove Company 227 Industrial Park Road South Pit...

Страница 2: ...ve unless in structions for doing so are given in this manual All other work should be done by a trained technician Do not operate your stove with the viewing door open The au ger will not feed pellets under these circumstances and a safety concern may arise from sparks or fumes entering the room Allow the stove to cool before performing any maintenance or cleaning Ashes must be disposed in a meta...

Страница 3: ...for Purchase Alternative Heat Main Heat Source Decoration Cost Other _________________________ What was the determining factor for purchasing your new USSC appliance _______ I have read the owner s manual that accompanies this unit and fully understand the Installation Operation and Maintenance of my new USSC appliance Print Name Signature Date Please attach a copy of your purchase receipt Warrant...

Страница 4: ... CUT HERE CUT HERE Fold Here Fold Here United States Stove Company P O Box 151 South Pittsburg TN 37380 Fold Here PLACE STAMP HERE ...

Страница 5: ...TM E 2779 EPA Method 28R FUEL CONSIDERATIONS Your pellet stove is designed and tested with premium grade pellets that comply with Pellet Fuels Institute PFI standards You can only burn premium grade pellets in this pellet heater Minimum of 40 lbs density per cubic ft 1 4 to 5 16 diameter length no greater than 1 5 not less than 8 200 BTU lb moisture under 8 by weight ash under 1 by weight and salt...

Страница 6: ... IMPROPER INSTALLATION The manufacturer will not be held responsible for damage caused by the malfunction of a stove due to improper venting or installation Call 800 750 2723 and or consult a professional installer if you have any questions CLEARANCES Your pellet stove has been tested and listed for installation in residential mobile home and alcove applications in accordance with the clearances g...

Страница 7: ...152 mm beyond the front and beyond each side of the fuel loading and ash removal openings Your heater will need a minimum 31 x 38 floor protector Floor protection must extend under and 2 in 50 8mm to each side of the chimney tee for an interior vertical installation see FIGURE 2 Canadian Installations require a minimum of 450 mm 17 7 beyond the front of the unit and 200mm 7 8 beyond each side of t...

Страница 8: ...LLET VENT TYPE A UL listed 3 inch or 4 inch type PL pellet vent exhaust system must be used for installation and attached to the pipe connector provided on the back of the stove use a 3 inch to 4 inch adapter for 4 inch pipe Connection at back of stove must be sealed using Hi Temp RTV Use 4 inch vent if the vent height is over 12 feet or if the installation is over 2 500 feet above sea level We re...

Страница 9: ...when adjacent to public walkways E Minimum 2 foot 0 61m clearance above any grass plants or other combustible materials F Minimum 3 foot 0 91m clearance from an forced air intake of any appliance G Minimum 2 foot 0 61m clearance below eves or overhang H Minimum 1 foot 0 3m clearance horizontally from combustible wall I Must be a minimum of 3 foot 0 091m above the roof and 2 foot 0 61m above the hi...

Страница 10: ...TEP 2 Unpack the top mount controls and ensure that the wiring harness shown is attached securely STEP 3 Connect the factory installed wiring harnesses to the control panel as shown STEP 4 Attach the control panel to the top of the stove as shown STEP 5 Secure with two sheet metal screws Assembly Instructions 10 ...

Страница 11: ...rfere with the house framing wiring etc 2 Install a non combustible hearth pad underneath the pellet stove This pad should extend at least 6 152mm in front of the unit 3 Place the pellet stove approximately 15 381mm away from the interior wall 4 Locate the center of the exhaust pipe of your unit This point should then be extended to the interior wall of your house Once you have located the center ...

Страница 12: ...ir Intake with approved cap 6 152mm Clearance to Combustibles Floor Protector 6 152mm Clearance Front Figure 9 6 152 mm Clearance Wall to Back of Unit Wall Thimble Exhaust Vent 45 Elbow or Listed Termination Rodent Mesh Cap Combustion Air Intake with approved cap 12 300mm Existing Floor Combustible Non Combustible Floor Protection 6 152 mm 12 ...

Страница 13: ...ion air intake pipe 6 Secure all vent joint connections with 3 screws Seal the exhaust vent joint connections with high temperature silicone sealant 7 Install a tee with a cleanout on the exhaust pipe found at the rear of your unit 8 Install approved vent upward through the ceiling When you pass through the combustible framing ensure that the appropriate ceiling fire stop is used You must maintain...

Страница 14: ...te the center of the exhaust pipe at the back of the unit Line up the center with the same spot on the exterior wall a cut a 7 178mm diameter hole through the wall 7 Install the wall thimble refer to the instructions which come with the wall thimble 8 Install an approved exhaust vent through the wall be sure to make sure that 3 75mm clearances to combustibles are maintained 9 Secure all vent joint...

Страница 15: ...DIRECT TEMP VENT SYSTEM FOR PELLET STOVE HEATERS UP AND OUT HORIZONTAL TERMINATION KIT Images courtesy of Selkirk STRAIGHT OUT HORIZONTAL TERMINATION KIT STRAIGHT OUT HORIZONTAL TERMINATION KIT Installation 15 ...

Страница 16: ...iteria must be met The unit must be secured to the floor using lag bolts in the holes provided in the pedestal base Ensure that the unit is permanently electrically grounded to the chassis of your home with 18 gauge copper wire All exhaust systems must have a spark arrestor IT IS MANDATORY TO TAKE THE COMBUSTION AIR FROM THE OUTSIDE WHEN INSTALLING THIS UNIT IN AIR TIGHT OR MANUFACTURED MOBILE HOM...

Страница 17: ...Installation SELKIRK DIRECT TEMP VENT SYSTEM FOR PELLET STOVE HEATERS Images courtesy of Selkirk 17 ...

Страница 18: ...N The C F button changes the two digit display from degrees Celsius to degrees Fahrenheit D MODE M T BUTTON The Mode of the stove can be switched between manual and controlled with a Thermostat Separate LEDs to the left of the two digit display indicate the mode of operation Manual or T Stat The stove has to be in normal operation to be switched from Manual to T Stat mode Manual mode operates acco...

Страница 19: ...ore being placed in hopper to remove most fines Binders Some pellets are produced with materials to hold the together or bind them High ash content Poor quality pellets will often create smoke and dirty glass They will create a need for more frequent maintenance You will have to empty the burn pot plus vacuum the entire system more often Poor quality pellets could damage the auger We cannot accept...

Страница 20: ...L TIMES EXCEPT WHEN REFILLING DO NOT OVERFILL HOPPER SHUTDOWN PROCEDURE Turning your stove off is a matter of pressing the POWER button on the display board The green light will turn back to red when the POWER button is pushed The auger motor will stop and the blowers will continue to operate until the internal firebox temperatures have fallen to a preset level 1 Your stove is equipped with a high...

Страница 21: ...Exchanger There is a clean out plate on both sides of the heat exchanger that need to be removed to clean fly ash out of the heat exchanger The cleanouts are located inside the cabinet doors on the lower front corners of the heat exchanger If a vacuum is used to clean your stove we suggest using a vacuum designed for ash removal Some regular vacuum cleaner i e shop vacs may leak ash into the room ...

Страница 22: ... any remaining pellets from the hopper and the auger feed system Scoop out the pellets and then run the auger until the hopper is empty and pellets stop flowing this can be done by pressing the ON button with the viewing door open Vacuum out the hopper Thoroughly clean the burn pot and firebox It may be desirable to spray the inside of the cleaned hopper with an aerosol silicone spray if your stov...

Страница 23: ...should be placed on a non combustible floor or on the ground well away from all combustible materials pending final disposal If the ashes are disposed of by burial in soil or otherwise locally dispersed they should be retained in the closed container until all cinders have been thoroughly cooled Do not place other waste in the same container SMOKE AND CO MONITORS Burning wood naturally produces sm...

Страница 24: ...his must be brushed clean The exhaust fan can be found behind the left side panel facing the front of the heater the circulation fan can be found behind the right side panel To access the igniter remove the air inlet tube and cover 2 screws The auger motor is located in the center rear of the unit Note When cleaning take care not to damage the fan blades Figure 26 Heat Exchanger Cleaner Handle Cir...

Страница 25: ...ossible Causes Possible Remedies Unplug stove first when possible 1 The convection blower is overheating and tripping the internal temperature shutoff Clean any dust off of the windings and fan blade If oiling the blower does not help the blower may be bad 2 The stove is being left on the highest setting for extended periods of time If operating the heater on the highest heat setting the room temp...

Страница 26: ...the gray wires to the air switch 6 Combustion blower failure With the stove on check to see if the combustion blower is running If it is not you will need to check for power going to the combustion blower It should be a full current If there is power the blower is bad If there is not see 8 7 Control board not sending power to combustion blower If there is no current going to the combustion blower ...

Страница 27: ...the motor is bad 8 The Proof of Fire POF thermodisc has malfunctioned Temporarily bypass the POF thermodisc by disconnecting the two wires and connecting them with a short piece of wire Then plug the stove back up If the stove comes on and works you need to replace the POF thermodisc This is for testing only DO NOT LEAVE THE THERMODISC BYPASSED Your blowers will never shut off and if the fire went...

Страница 28: ...ger tube for signs of damage such as burrs rough spots or grooves cut into the metal that could have caused a jam 7 The auger motor has failed Remove the auger motor from the auger shaft and try to run the unit If the motor will turn the shaft is jammed on something If the motor will not turn the motor is bad STOVE FEEDS PELLETS BUT WILL NOT IGNITE Possible Causes Possible Remedies Unplug stove fi...

Страница 29: ...UT FUEL FEED LIGHT COMES ON AS DESIGNED Possible Causes Possible Remedies Unplug stove first when possible 1 High limit switch has tripped or is defective Wait for the stove to cool for about 30 45 minutes Locate the High Limit thermodisc and press the reset button on the back of it If the heater will not restart check the thermodisc to see if it s bad To test if the thermodisc is bad you can bypa...

Страница 30: ...RK AND HAS BLACK TIPS AFTER STOVE HAS BEEN ON FOR A WHILE THE BURNPOT OVERFILLS Possible Causes Possible Remedies Unplug stove first when possible 1 Stove or vent pipe is dirty which restricts airflow through the burnpot Follow all cleaning procedure in the maintenance section of the owner s manual 2 Vent pipe installed improperly Check to make sure the vent pipe has been installed according to th...

Страница 31: ...1 2 3 9 8 10 4 5 7 8 11 19 14 18 34 17 15 16 13 12 21 22 21 23 24 33 6 25 20 32 26 27 28 Parts Diagram 31 ...

Страница 32: ...167 Gasket Convection Blower 1 18 80622 Blower Convection 1 19 80604 Igniter 1 20 80676 PCBA Controller 1 21 891998 Bushing 2 22 891999 Auger 1 23 80606 Motor Auger 1 24 80491 Micro Switch 1 25 892344 Top Assembly 1 26 892264 Panel Left Cabinet 1 27 892345 Panel Right Cabinet 1 28 892037 Hearth Trim 1 29 892276 Ashley Grill Opening 1 30 851714 Ashley Logo 1 31 892064 Decorative Log 1 32 892199 Hou...

Страница 33: ...Wiring Diagram 33 ...

Страница 34: ...ty or any implied warranty 2 Should the heater be replaced by United States Stove Company free of charge all further warranty obligations are thereby met 3 Parts and or service replacements made under the terms of this warranty are warranted only for the remaining period of the original heater warranty 4 Without speci c written exclusionary waivers no one has authority to add to or vary this limit...

Страница 35: ...Notes ...

Страница 36: ... THE FULL MODEL NUMBER WHICH IS ON THE NAMEPLATE ATTACHED TO THE HEATER WHEN ORDERING REPAIR PARTS ALWAYS GIVE THE FOLLOWING INFORMATION AS SHOWN IN THIS LIST 1 THE PART NUMBER 2 THE PART DESCRIPTION 3 THE MODEL NUMBER AP5660 PE 4 THE SERIAL NUMBER ____________________ United States Stove Company 227 Industrial Park Road P O Box 151 South Pittsburg TN 37380 800 750 2723 WWW USSTOVE COM HOW TO ORDE...

Отзывы: