Sensor Unresponsive Settings
displays the Sensor Unresponsive Menu where you can configure the actions
the S530 takes if an ES becomes unresponsive.
EventSensor Slots
SiteBoss 530 - Internal Events Menu
A) Device Name [INTERNAL]
B) Contact Closure 1 [unnamed]
C) Contact Closure 2 [unnamed]
Enter your Selection:
The display for each EventSensor will vary depending on configuration. EventSensors can be configured with
varying combinations of the following I/O types. Refer to the
section in the Features
chapter for more information.
•
•
•
•
•
Sensor Unresponsive Settings
SiteBoss 530 - Sensor Unresponsive Menu
A) Sensor Unresponsive Timeout [30]
B) Sensor Unresponsive Actions []
C) Sensor Unresponsive Trap Number [50]
D) Sensor Unresponsive Class [Info]
Sensor Unresponsive Timeout
sets the time (10 - 65535 seconds) to wait before declaring a non-
communicative EventSensor unresponsive. Default setting is 30.
Sensor Unresponsive Actions
displays the Actions List, a menu where the action string for the event is
configured. This field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more
actions have been configured. Refer to
in the Features chapter for more information.
Sensor Unresponsive Trap Number
sets the number to be sent with any SNMP traps for this event. Default is
50, but trap number can also be set in the range of 1000 – 1199 as needed.
Sensor Unresponsive Class
sets the class for the alarm. When this option is selected, a list of the classes
previously defined in the
is displayed, from which you can select one to be assigned to this event.