Asentria SiteBoss 530 User Manual
1
Quick Start
What's Included
This chapter is a brief guide to help get your SiteBoss 530 (S530) up and running quickly.
Hardware Needed
•
Asentria SiteBoss 530
•
15VDC power adaptor (Included if AC power option)
•
DC power source (if DC power option)
•
Computer with DB9 RS-232 Serial port and terminal emulation software
•
Ethernet cable
•
RJ45 M-M unshielded serial cable and RJ45/DB9 straight thru adapter (Included)
•
A PC running any type of SNMP trap management software, if S530 will be sending SNMP traps as event
actions.
Information Needed
•
IP address(es) to assign to the S530
•
Subnet mask
•
Default router IP or gateway router IP address if on a WAN (Optional)
•
IP address of a PC running any type of SNMP trap management software, if S530 will be sending SNMP traps as
event actions.
Connecting
Cables and Power
1. Connect the RJ-45 serial cable and DTE adaptor together, and connect to serial port I/O2 of the S530 and
the COM1 of a PC or laptop running any terminal emulator.
2. Connect the attached ground wire securely to an appropriate earth ground (this is essential).
3. Connect an Ethernet cable, if available, into the RJ-45 jack labeled ETH1.
4. Connect the power supply to the unit (see Power Requirements section).
Power Requirements
The S530 is configured with one of two types of power connectors: AC or DC.
If configured for AC, the unit uses a barrel connector for connecting to the 15VDC power adapter shipped with the
unit.
If configured for DC, the unit is configured with a 4-pin Molex connector for use with a DC power source. The unit
is shipped with the cables and instructions for direct connection to a DC power source. The instructions are
shown below, in case they are missing from the box.
Note:
This instruction sheet describes connection of the provided –48V wiring harness kit to the source
power supply. This unit should be assembled and installed by a qualified technician who can ensure the power
source is an isolated, SELV (Safety Extra Low Voltage) circuit. There are two versions of the harness using
different wiring colors as shown below.
Note:
Because the S530 is generally considered to be "permanently connected“, safety standards require
that an appropriate disconnect device shall be provided as part of the building installation. The -48VDC input
should be protected by an external 2A Slow Blow Fuse conforming to CSA/UL 248-14, IEC 60127-4/2, at the
power supply or within the building circuitry as appropriate. The input DC power current limiting fuse circuit is
provided for by the end user, and is required for unit operation in compliance with safety agency approvals.
One example of a compliant fuse for the -48V input is a Littelfuse 239P series, 2 amp fuse with a 250 VDC
minimum voltage rating and interrupt rating 10,000 amps at 125 VAC, 0.7 to 0.8 power factor and 100 amps at
125VAC, 0.7-0.8 power factor.