The S530 can be ordered with any of the following different internal I/O devices (on Expansion Cards) or can be
connected to a number of external Type2 EventSensor devices as described in this section. The setup menus are the
same regardless of whether the device is internal or external to the S530. If using external Asentria Type2
EventSensors with the S530, please refer to the Type2 EventSensor User Manual for a full description of each type of
sensor and hardware specifications.
Input
Output
Contact Closure Setup
Below is a representative Events Menu showing a Type2 EventSensor ES-8C to monitor contact closures:
Contact closures (CC) sense the state of a circuit. A weak voltage is applied to the source pin and if pulled to ground
by a connection on the circuit, the sensor reports a "closed" state. If it remains high, the sensor reports an "open"
state. All of the CCs share a common ground. The contact closures may be configured to alarm in either the open or
closed state, depending on the needs of the attached devices.
Sensor Name
is an alphanumeric field that allows you to name this contact closure. (Max length 60 chars)
Contact Closure Enabled
is an ON/OFF toggle to enable this contact closure.
Event State
is an OPEN/CLOSED toggle that determines whether an event will be triggered when the contact closure
circuit is opened or closed. The default state is CLOSED.
Threshold
is the number of seconds (0-255) the sensor must remain in the event state before an actual event occurs.
Event State / Return to Normal Actions
displays the Actions List, a menu where the action string for the event is
configured. This field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions
have been configured. Refer to the
Event State / Return to Normal Class
sets the class for the event. When this option is selected, a list of the classes
previously defined in the
is displayed, from which you can select one to be assigned to this event.
Event / Return to Normal Trap Number
sets the trap number which can be useful when using SNMP trap managers
that employ a trap numbering system to help identify incoming traps. The default trap number for Contact Closure
Events is 110, but any number in the alternate range of 1000 – 1199 can be used.
Active Alarm Alias
is a customized name representing the active alarm state, used when reporting active events for
this sensor.
SiteBoss 530 - External Contact Closure Event 1
Device Number: 2 Device ID: ESIO00217 Device Name: unnamed
A) Sensor Name [CC1]
B) Contact Closure Enabled [OFF]
C) Event State [CLOSED]