Asentria SiteBoss 530 User Manual
109
Type2 EventSensor™ Setup
The S530 supports up to 16 Type2 EventSensors. Type2 EventSensors are different than the Type1 EventSensors
sold by Asentria but support similar and expanded monitoring capabilities. Type2 EventSensors work only with the
SiteBoss and TeleBoss line of Asentria products. Data-Link and SNMP-Link products use only the Type1 Event
Sensors. (The two Types are not compatible.) However, configuration of Type2 EventSensors within the
EventSensor Device Settings menu is identical to how Type1 EventSensors are configured.
Connections
Type2 EventSensors connect to the host unit and each other via an RJ45/9-pin mini DIN cable. The 9-pin mini DIN
cable end of the EventSensor cable plugs in to the SensorJack port on the back panel of the S530. The RJ45 end of
that cable plugs in to the Type2 EventSensor RJ45 port labeled Control. Additional Type2 EventSensors are chained
together using Cat-5 straight-thru cable from the Sensor port on the first EventSensor, to the Control port on the next
EventSensor. Be sure to set the DIP switches for each additional EventSensor so that each occupies it’s own slot as
per the chart below.
Different configuration arrays of Type2 Event Sensors are fully described with graphics in the EventSensor Datasheet
which is available from either Asentria Sales (
DIP Switch Settings
Defines up to 16 address locations. Note that the DIP switch is numbered from left to right, 1 through 4. The Most
Significant Bit (MSB) is switch location 1.
1 = DIP Switch up 0 = DIP Switch down
DIP SW
Slot
DIP SW
Slot
DIP SW
Slot
DIP SW
Slot
0000
= 1
0100
= 5
1000
= 9
1100
= 13
0001
= 2
0101
= 6
1001
= 10
1101
= 14
0010
= 3
0110
= 7
1010
= 11
1110
= 15
0011
= 4
0111
= 8
1011
= 12
1111
= 16
Configuration
Refer to the
section for configuration instructions.
Calibration of Temperature and Humidity Sensors
Temperature and humidity settings can be calibrated in ES-T and ES-TH Type2 EventSensors via Setting Keys (no
menu options available to do this). This gives a user the ability to make calibration adjustments to fine-tune the
accuracy of the reported reading, if desired. This process is transparent and provides temperature and humidity
readings that are consistent with other devices that measure temperature and relative humidity in the same
environment. This mechanism uses two calibration points to set up a slope and offset that is used to adjust the
measured reading.
This feature is enabled by changing Setting Key values only; the text menu and web interface do not provide access
to these keys. The default Setting Keys are:
event.sensor[x].humid[y].callowin
=0
event.sensor[x].humid[y].callowout
=0
event.sensor[x].humid[y].calhighin
=100
event.sensor[x].humid[y].calhighout
=100
event.sensor[x].temp[y].callowin
=0
event.sensor[x].temp[y].callowout
=0
event.sensor[x].temp[y].calhighin
=100
event.sensor[x].temp[y].calhighout
=100