Asentria SiteBoss 530 User Manual
41
Data Alarm/Filter
n
Settings
SiteBoss 530 - Settings For Data Alarm/Filter 1
A) Alarm/Filter Enable [OFF]
B) Alarm/Filter Mode [ALARM]
C) Alarm/Filter Name []
D) Alarm/Filter Equation []
E) Threshold [1]
F) Auto-Clear when Threshold Reached [ON]
G) Alarm Counter Clear Interval [12 HOURS]
H) Alarm Counter Reset Time [00:00]
I) Actions []
J) Class [Info]
K) Data Alarm Trap Number [503]
L) Clear This Alarm Counter Now
Alarm/Filter Enable
is an ON/OFF toggle to enable this data event monitor. Default setting is OFF.
Alarm/Filter Mode
toggles between ALARM and FILTER to indicate whether the S530 will recognize this data
event as an Alarm and take some action, or as a Filter and either accept or reject the data string. Default setting
is ALARM.
Alarm/Filter Name
sets the name for the event monitor. This name is reported with the specified actions. (Max
length 16 chars)
Alarm/Filter Equation
defines the event equation using the event fields defined in the previous menu. (Max
length 160 chars) Refer to the
Configuring Data Alarm Equations
section in the Features chapter for more
information.
Threshold
sets the number of times the event equation must be matched before an event is triggered. If the
event counter is allowed to grow beyond the threshold, the unit will not trigger an event again until after the
counter is reset. Default setting is 1.
Auto-Clear when Threshold Reached
is an ON/OFF toggle to control whether the unit will clear the event
counter each time the threshold is met. Default setting is ON.
Alarm Counter Clear Interval
sets an interval at which the unit should clear the match counter for an individual
data event. Available options are: 2 hours, 4 hours, 6 hours, 8 hours, 12 hours, Daily, and Never. The first clear
occurs at midnight. Default setting is 12 Hours.
Alarm Counter Reset Time
sets the time at which the daily clear should take place if it is enabled in the Alarm
Counter Clear Interval. This value is in 24-hour format. Default setting is 00:00.
Actions
displays the
, a menu where the action string for the event is configured. This field will be
empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been configured.
Refer to
in the Features chapter for more information.
Class
sets the class for the alarm. When this option is selected, a list of the classes previously defined in the
is displayed, from which you can select one to be assigned to this data alarm.
Data Alarm Trap Number
sets the number to be sent with any SNMP traps for this event. Default is 503, but trap
number can also be set in the range of 1000 – 1199 as needed.
Clear This Alarm Counter Now
allows you to manually clear the counter for the selected data alarm. This
happens as soon as this option is selected, so make sure you really want to clear the counter before selecting it.