104
High Event Humidity
sets the humidity at which the High Event Actions will be triggered.
High Event Actions
displays the Actions List, a menu where the action string for the event is configured. This field
will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been
configured. Refer to the
for more information.
High Trap Number
sets the trap number which can be useful when using SNMP trap managers that employ a trap
numbering system to help identify incoming traps. The default trap number for Humidity Events is 130, but any
number in the alternate range of 1000 – 1199 can be used.
High Event Class
sets the class for the alarm. When this option is selected, a list of the classes previously defined in
is displayed, from which you can select one to be assigned to this event.
Return to Normal Settings Setup
SiteBoss 530 - External Humidity Event Settings
Device Number: 3 Device ID: ESTH00042 Device Name: Test ES-TH
A) Return to Normal Event Actions []
B) Return to Normal Event Trap Number [130]
C) Return to Normal Event Class [Info]
Return to Normal Event Actions
displays the Actions List, a menu where the action string for the event is
configured. This field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions
have been configured. Refer to the
Return to Normal Event Trap Number
sets the trap number which can be useful when using SNMP trap managers
that employ a trap numbering system to help identify incoming traps. The default trap number for Humidity Events is
130, but any number in the alternate range of 1000 – 1199 can be used.
Return to Normal Class
sets the class for the event. When this option is selected, a list of the classes previously
is displayed, from which you can select one to be assigned to this event.
Analog Voltage / Current Sensor Setup
Below is a representative Events Menu showing an 8V Expanson Card to monitor 8 analog voltage inputs. Analog
current inputs, such as on an 8mA Expansion Card use an identical menu.
SiteBoss 530 - External Events Menu
Device Number: 2 Device ID: 20020000
A) Device Name [unnamed]
B) Analog Input 1
C) Analog Input 2
D) Analog Input 3
E) Analog Input 4
F) Analog Input 5
G) Analog Input 6
H) Analog Input 7
I) Analog Input 8
J) EventSensor Reporting Enabled [OFF]
K) Clear Settings for This EventSensor
Enter your Selection:
Analog voltage sensors provide individual voltage sensing for ranges from –60/+60VDC. Analog current sensors
provide individual voltage sensing for ranges from 4-20mA. These sensors can be used in various applications, from
monitoring a power supply to verifying RS232 voltage levels.
Device Name
is the option name given to the sensor. Default is unnamed.
displays a menu where each analog voltage sensor can be configured.