background image

Ascon Tecnologic - e33B - OPERATING INSTRUCTIONS - PAG. 10

Phase

off

off

ON

0

1

2

3

Temp.

ddi/dSd

time to defrost Phases 0, 1

Defrost

off

off

DT0

dtE

dtS

Cool

ot

Defrost

dF

SP + rd

SP

Pr1

rd

EP

DT1

DT2

DT3

time to defrost Phase 2

time to defrost Phase 3

time

ON

ON

ON

Example “dynamic defrost intervals system” with a reduction 

ddd

 = 

40%

 and end defrost by temperature.

Defrost by evaporator temperature 

The instrument starts a defrost cycle when the evaporator 
temperature (

EP

 probe) goes below the 

dtF

 programmed 

temperature for 

dSt

 programmed time.

This modality can be used to guarantee a defrost if the 
evaporator reaches very low temperatures that normally re-
sult symptomatic of a bad thermal exchange in comparison 
to the normal working conditions.
When 

dtF

 = 

-99.9

 the function is disabled.

Defrost by continuous compressor running time

The instrument start a defrost cycle when the compressor is 
turned ON continuously for the time 

dcd

.

This function is used because the continuous operation for an 
extended period of the compressor is usually symptomatic of 
a bad thermal exchange in comparison to the normal work-
ing conditions.
When 

dcd

 = 

oF

 the function is disabled.

5.8.2 

Manual defrost

To start a manual defrost cycle, press the key 

/  when 

in Normal operation mode and keep it pressed for about 5 s 
after which, if the conditions are correct, the LED   lights up 
and the instrument performs a defrost cycle.
To stop a defrost cycle, press the key 

/  during the de-

frost and keep it pressed for about 5 seconds.

5.8.3 

End of defrosts

The defrost cycle duration can be time based, or, using the 
evaporator probe (configured as 

EP

) when a specific tem-

perature is reached.
If the evaporator probe is not used, the cycle time is set 
by parameter 

ddE

 (setting 

ddE

 = 

oF

 the Time-interval or 

Manual defrosts are disabled).
If, on the other hand, the evaporator probe is used, the end 
of defrosting occurs when the temperature measured by this 
probe configured as 

EP

 exceeds the temperature set with 

parameter 

dtE

.  If 

dtE

 temperature is not reached within the 

time set at parameter 

ddE

, the defrost is anyway interrupted.

To avoid unnecessary defrosting when the evaporator tem-
perature is high, parameter 

DtS

 allows to set the temperature 

related to the 

EP

 probe under which defrosts are possible.

Therefore, in the indicated modes, if the temperature meas-
ured by the 

EP

 probe is higher than the one set at parameter 

dtS

 and also 

dtE

 defrosts are inhibited.

dtE
dts

Defrost

dF

off

off

off

ON

ON

A

B

Temp.

time

C

(NO defrost)

dde

ddi/dSd

(Defrost)

ddi/dSd

ddi/dSd

ddi

(Defrost)

EP

Example: Defrost 

A

 ends due to reaching of temperature 

dtE

, defrost 

B

 ends at the end of the 

ddE

 time as the 

temperature 

dtE

 is not reached, defrosting 

C

 does not take 

place as the temperature is higher than 

dts

.

dtE

dts

off

off

off

off

ddi/dSd

ON

ON

ON

time

ddi

(Defrost)

dde

Defrost

dF

Temp.

EP

Example of electric defrost with evaporator temperature 
control: the defrost end after 

ddE

 programmed time.  During 

defrost the 

dF

 output switch ON/OFF to control evaporator 

temperature in heating mode with set point 

dtE

 and 1° dif-

ferential (Hysteresis).

The active defrost is shown on the instrument display with 
the lighting up of the LED  .
At the end of defrosting, it is possible to delay the new com-
pressor start up (output 

ot

) at the time set in parameter 

dtd

 

to allow the evaporator to drain.  During this delay, the LED 

 flashes to indicate the draining state.

5.8.4 

Intervals and defrosts duration in case of 
evaporator probe error

In event of evaporator probe error the defrosts occur at inter-
vals 

dEi

 and duration 

dEE

.

In case an error occurs when the time remaining to the start 
or the end of defrost is lower than the one normally set with 
the parameters related to error probe conditions, the start or 
the end takes place with the shortest time.
These functions are provided because when the 

EP

 evapo-

rator probe is used, the set defrost endurance time is usually 
longer than necessary (the time 

ddE

 is a security time-out) 

and in case is used the “Dynamic Intervals Defrost System” 
the interval is usually set more longer than what is normally 
programmed into instruments that do not have the function.

5.8.5 

Display lock during Defrost

Through parameters 

ddL

 and 

AdA

 it is possible to define the 

display behaviour during defrost:

on 

The 

ddL

 parameter locks the display at the last 

Pr1

 

temperature reading during all the defrost cycle until, 
at the end of defrost, the temperature has not reached 
the lock value or the value [

SP

 + 

rd

] or is elapsed the 

time set at parameter 

AdA

;

oF 

The display continues showing the temperature meas-
ured by the 

Pr1

 probe during the defrost cycle.

Содержание e33B

Страница 1: ...ration through stopping the compressor electric heating or hot gas cycle inversion The controller is equipped with special defrost optimization functions and with other functions that can be used to o...

Страница 2: ...Stand by mode this is the only lighted LED In programming mode while the parameter code is displayed the dot indicates the parameter protection level not protected lit up protected flashing and hidde...

Страница 3: ...ial test keeping it pressed for 5 s In this way it is possible to access all the parameters verify and modify the parameter tPP 2 4 Customized mode parameter programming parameters programming level T...

Страница 4: ...d rule must adopt all the necessary protective measures The instrument MUST NOT BE USED in dangerous environ ments flammable or explosive without adequate protections The instrument used with NTC 103A...

Страница 5: ...1 A Out 3 2 1 A 60730 EN UL 5 FUNCTIONS 5 1 ON Stand by function Once powered the instrument can assume 2 different conditions ON Means that the controller uses the control functions STAND BY Means t...

Страница 6: ...always closed 5 3 Measure and display configuration With parameter iuP it is possible to select the tempera ture engineering unit and the desired measure resolution C0 C 1 C1 C 0 1 F0 F 1 F1 F 0 1 The...

Страница 7: ...that is NO in normal operation then closed during the alarm AL To control an alarm that cannot be silenced through a contact that is NO in normal operation then closed during the alarm An To control a...

Страница 8: ...s automatic switching between the three Normal Eco Turbo modes described at the paragraph Operating modes The time protections described in the next paragraph PP1 PP2 PP3 always work on the ot configu...

Страница 9: ...a chines in which is required the maximum evaporator efficiency at each compressor cycle To enable automatic defrost at intervals after setting the ddC parameter as desired between rt ct or cS with th...

Страница 10: ...related to the EP probe under which defrosts are possible Therefore in the indicated modes if the temperature meas ured by the EP probe is higher than the one set at parameter dtS and also dtE defros...

Страница 11: ...emperature alarms Hi and Lo External alarm AL Door open oP The alarm functions acts on LED on the internal buzzer if present and configured by the obu parameter and on the desired output if configured...

Страница 12: ...The instrument can signal an alarm external to the instrument using the digital input setting iFi 4 or 5 The instrument signals the alarm turning ON the alarm LED and display ing AL label alternated...

Страница 13: ...f some instruments which need to have the same parameters con figuration or to keep a copy of the parameters settings of an instrument and allow its rapid retransmission The same device allows to conn...

Страница 14: ...ck 3 Open Door with Fan and Output Lock 4 External Alarm 5 External alarm with control output disabling 6 Normal Eco select 7 On Stand by select 8 Start a Turbo cycle 2 15 iti Digital Input Delay oF D...

Страница 15: ...n disabled 1 59 s 1 99 min 5 42 FtF Fan time deactivation with ot output compressor OFF oF Function disabled 1 59 s 1 99 min oF 43 FFL High temperature fan deactivation 99 9 999 C F 10 0 44 FLF Low te...

Страница 16: ...otu Time relative to auxiliary output oF Function disabled 1 59 s 1 99 min oF 67 tUF Key Function oF No function 1 Eco Mode direct selection turn OFF the showcase light if configured 2 Switch ON Swit...

Страница 17: ...faults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1 Electrical characteristics Power supply 230 VAC 115 VAC 12 VAC VDC 10...

Страница 18: ...C 103AT11 11 INSTRUMENT ORDERING CODE MODEL e33B Instrument with mechanical keyboard a POWER SUPPLY D 230 VAC C 115 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 H Out1 Relay SPST NO 16A AC1 for resistive loads R...

Страница 19: ...Ascon Tecnologic e33B OPERATING INSTRUCTIONS PAG 19...

Отзывы: