Ascon Tecnologic - e33B - OPERATING INSTRUCTIONS - PAG. 5

4.3 

Electrical connections

Carry out the electrical wiring by connecting only one wire to 
each terminal, according to the following diagram, checking 
that the power supply is the same as that indicated on the 
instrument and that the load current absorption is no higher 
than the maximum electricity current permitted.
As the instrument is built-in equipment with permanent con-
nection inside housing, it is not equipped with either switches 
or internal devices to protect against current overloads: the 
installation will include an overload protection and a two-
phase circuit-breaker, placed as near as possible to the in-
strument and located in a position that can easily be reached 
by the user and marked as instrument disconnecting device 
which interrupts the power supply to the equipment
It is also recommended that the supply of all the electrical cir-
cuits connected to the instrument must be protect properly, us-
ing devices (ex. fuses) proportionate to the circulating currents.
It is strongly recommended that cables with proper insulation, 
according to the working voltages and temperatures, be used.
Furthermore, the input cable of the probes has to be kept sepa-
rate from line voltage wiring.  If some cables used for the wiring 
should be shielded, it is recommended to c

onnect the shield  

to ground at one side only

.

Whether the instrument is a 12 V version (Power supply code 
F) it is recommended to use an external TCTR transformer, or 
with equivalent features (class II insulation) and to use only one 
transformer for each instrument because there is no insulation 
between supply and input

D

D

We recommend that a check should be made that the 
parameters are those desired and that the application 
functions correctly 

before connecting the outputs to 

the actuators

 so as to avoid malfunctioning that may 

cause irregularities in the plant that could cause dam-
age to people, things or animals.

4.3.1 

Electrical wiring diagram

Internal

Buzzer

Pr1

Pr3

Pr2

Digital

Input

Power

supply

INPUTS

NO

NO

NO

NC

C

Out2

Out1

Out3

OUTPUTS

(12 A max. for removable connectors models)

16 FLA

96 LRA

15 A Res.

EN

30 (15) A

61810

Out 1 (H):

15 (15) A

5 FLA

30 LRA

12 A Res.

16 (9) A

Out 1 (R):

10 (4) A

10 A Res.

8 (3) A

Out 2:

8 (4) A

2 A Gen. Use

5 (1) A

Out 3:

2 (1) A

60730

EN

UL

5.  FUNCTIONS

5.1 

ON/Stand-by function

Once powered the instrument can assume 2 different conditions:

ON

:  Means that the controller uses the control functions.

STAND-BY:   

Means that the controller uses no control function and 
the display is turned off except for the Stand-by LED.

The transition between Standby and ON is equivalent to 
power ON the instrument providing the electrical power
In case of power failure, the system always sets itself in the 
condition it was in before the black-out
The ON/Stand-by function can be selected:

 

With the key 

/  pressed for 1 s if 

tUF

 = 

3

;

 

Using the Digital Input if parameter 

iFi

 = 

7

;

5.2 

Normal, Economic and Turbo operation

The instrument allows to pre-set 5 different control Set 
points, 3 of which (

SP1

SP2

SP3

) are 

Normal

, one 

SPE 

is 

Economic

 (or Eco) and one 

SPH

 

Turbo

.

Associated with each Setpoint there is the relative differential 
(hysteresis): 

Normal

 - 

rd

Eco

 - 

rEd

 and 

Turbo

 - 

rHe

.

As already explained at paragraph “

2.1 - Quick setting of the 

normal Set Point

” the “

Normal

” operating set point can be 

only 

1

 (

Sp1

 if 

tEd

 = 

1

) or selectable between 3 preset values (

SP1

SP2

SP3

 if 

tEd

 = 

2

).

Note: 

In the following examples the Set point is generally 
indicated as 

SP

, however the instrument 

operates on 

the basis of the active Set Point

.

5.2.1 

Normal/Eco operation selection

This function can be used when you need to switch two func-
tional temperatures (eg. Day/Night or week-day/week-end).

Pr1

Temp.

SPE

SP

Door

rd

rEd

iEt

time

Normal

DAY (Shop open)

DAY (Shop open)

NIGHT (Shop closed)

Normal

eco

Out

L1

ON

OFF

ON

Example of automatic 

ECO

/

Normal

 mode activation.  during 

the business hours the door is opened frequently and the 
controller remains in 

Normal

 mode.  After the 

iEt

 time has 

elapsed since the door has not been opened anymore, the 
controller switches to 

ECO

 mode.  As soon as the door is 

opened again, the controller returns to 

Normal

 mode.

The Normal/Eco operation can be selected in manual mode:

 

Using the 

/  key if parameter 

tUF

 = 

2

;

 

Using the Digital Input if parameter 

iFi

 = 

6

.

The Normal/Eco operation can be selected in automatic mode:

 

Elapsed the 

iEt

 time after the door has been closed 

(Normal/Eco switching).

 

At door opening if the 

SPE

 Setpoint is activated by 

iEt

 

parameter (Eco/Normal switching).

 

Elapsed the 

itt

 time after the door has been closed and 

from the activation of 

SPE

 Setpoint (Eco mode) by 

iEt

 

parameter (Eco/Normal switching).

To use this function, it is necessary to set the Digital Input as: 

iFi

 = 

1

2

 or 

3

 (door open Input).

Содержание e33B

Страница 1: ...ration through stopping the compressor electric heating or hot gas cycle inversion The controller is equipped with special defrost optimization functions and with other functions that can be used to o...

Страница 2: ...Stand by mode this is the only lighted LED In programming mode while the parameter code is displayed the dot indicates the parameter protection level not protected lit up protected flashing and hidde...

Страница 3: ...ial test keeping it pressed for 5 s In this way it is possible to access all the parameters verify and modify the parameter tPP 2 4 Customized mode parameter programming parameters programming level T...

Страница 4: ...d rule must adopt all the necessary protective measures The instrument MUST NOT BE USED in dangerous environ ments flammable or explosive without adequate protections The instrument used with NTC 103A...

Страница 5: ...1 A Out 3 2 1 A 60730 EN UL 5 FUNCTIONS 5 1 ON Stand by function Once powered the instrument can assume 2 different conditions ON Means that the controller uses the control functions STAND BY Means t...

Страница 6: ...always closed 5 3 Measure and display configuration With parameter iuP it is possible to select the tempera ture engineering unit and the desired measure resolution C0 C 1 C1 C 0 1 F0 F 1 F1 F 0 1 The...

Страница 7: ...that is NO in normal operation then closed during the alarm AL To control an alarm that cannot be silenced through a contact that is NO in normal operation then closed during the alarm An To control a...

Страница 8: ...s automatic switching between the three Normal Eco Turbo modes described at the paragraph Operating modes The time protections described in the next paragraph PP1 PP2 PP3 always work on the ot configu...

Страница 9: ...a chines in which is required the maximum evaporator efficiency at each compressor cycle To enable automatic defrost at intervals after setting the ddC parameter as desired between rt ct or cS with th...

Страница 10: ...related to the EP probe under which defrosts are possible Therefore in the indicated modes if the temperature meas ured by the EP probe is higher than the one set at parameter dtS and also dtE defros...

Страница 11: ...emperature alarms Hi and Lo External alarm AL Door open oP The alarm functions acts on LED on the internal buzzer if present and configured by the obu parameter and on the desired output if configured...

Страница 12: ...The instrument can signal an alarm external to the instrument using the digital input setting iFi 4 or 5 The instrument signals the alarm turning ON the alarm LED and display ing AL label alternated...

Страница 13: ...f some instruments which need to have the same parameters con figuration or to keep a copy of the parameters settings of an instrument and allow its rapid retransmission The same device allows to conn...

Страница 14: ...ck 3 Open Door with Fan and Output Lock 4 External Alarm 5 External alarm with control output disabling 6 Normal Eco select 7 On Stand by select 8 Start a Turbo cycle 2 15 iti Digital Input Delay oF D...

Страница 15: ...n disabled 1 59 s 1 99 min 5 42 FtF Fan time deactivation with ot output compressor OFF oF Function disabled 1 59 s 1 99 min oF 43 FFL High temperature fan deactivation 99 9 999 C F 10 0 44 FLF Low te...

Страница 16: ...otu Time relative to auxiliary output oF Function disabled 1 59 s 1 99 min oF 67 tUF Key Function oF No function 1 Eco Mode direct selection turn OFF the showcase light if configured 2 Switch ON Swit...

Страница 17: ...faults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1 Electrical characteristics Power supply 230 VAC 115 VAC 12 VAC VDC 10...

Страница 18: ...C 103AT11 11 INSTRUMENT ORDERING CODE MODEL e33B Instrument with mechanical keyboard a POWER SUPPLY D 230 VAC C 115 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 H Out1 Relay SPST NO 16A AC1 for resistive loads R...

Страница 19: ...Ascon Tecnologic e33B OPERATING INSTRUCTIONS PAG 19...