Ascon Tecnologic - e33B - OPERATING INSTRUCTIONS - PAG. 3

2.2 

Standard mode parameters programming

To access the instrument function parameters when pass-
word protection is disabled, press the keys 

/  and 

/  

at the same time and keep them pressed for about 5 s, after 
which the display shows the code that identifies the first pro-
grammable parameter.  Press the 

/

 keys to display the 

desired parameter, then, pressing the 

/  key, the display 

shows the parameter code alternated to its value that can be 
changed with the 

 and 

 keys.

Once the desired value has been set, press 

/  again: the 

new value is stored and the display shows only the code of the 
selected parameter.  Pressing the 

/

 keys, it is now pos-

sible to select another parameter and change it as described.
To exit the program mode, press no keys for about 30 s or 
keep the 

/  key pressed for 2 s.

-15.5

sPH

-20.0

Previous

Parameter

Normal mode

Parameter select

(Program mode)

Parameter set

Next

Parameter

2 s

5 s

Increase

value

Decrease

value

Note: 

With parameters in which the variable to be set is a time, 
the least significant time unit (s when s/min, min when 
min/h) is displayed in negative form (with the sign -); the 
most significant time unit (m when s/min, h when min/h) 
is displayed as a positive value (without the sign).

2.3 

Parameter protection using a Password

The instrument has a parameter protection function using a 
password that can be personalised through the 

tPP

 parameter

To protect the parameters, set the desired password number 
in the parameter 

tPP

.

When the protection is active, press the keys 

/  and 

/  

at the same time and keep them pressed for about 5 s, after 
which the display shows 

r.p

.  Now press only the 

/  key, 

the display shows 

0

; using the 

/

 keys, insert the pro-

grammed password number and press the key 

/  again.

If the password is correct the instrument displays the code of 
the first parameter and it will be possible to program the in-
strument in the same way described in the previous section.
The password protection can be disabled by setting 

tPP

 = 

oF

.

spH

-15.5

0

Normal mode

Password

request

Parameter

(Program mode)

Correct password

inserted

2 s

5 s

Increase

value

Decrease

value

rp

Notes: 1. 

All parameters are configured by default at 
“protected” level so that setting the 

PP

 parameter 

protects all parameters with the password.

2. 

If the Password gets lost, just switch OFF and ON 
the instrument, push 

/  key during the initial 

test keeping it pressed for 5 s.  In this way it is 
possible to access all the parameters, verify and 
modify the parameter 

tPP

.

2.4 

Customized mode parameter programming 

(parameters programming level)

The password hides all the configuration parameters behind a 
factory set password to avoid unwanted changes to the con-
troller parameters.  To make a parameter accessible without 
having to enter the password when 

tPP

 password protection 

is activate, use the procedure that follows:
Enter the program mode using the 

tPP

 Password and select the 

parameter that must be accessible (no password protection).
Once a parameter is selected, if the 

dp LED flashes

 the 

parameter is programmable by entering the password (is 

protected

”).  If the 

dp LED is steady ON

 the parameter is 

programmable without password (is “

unprotected

”).

To change the parameter visibility, press the 

/  key and 

keeping it pressed also press the 

 button.

The 

dp LED

 changes its state indicating the new level of 

parameter accessibility (

ON

 = not protected;  

flashing

 = password protected).

In case some parameters are not protected, accessing 
the the programming mode the device first shows the not 
protected parameters, then the 

r.p

 parameter (through which 

will be possible to access the “protected” parameters).

Previous

Param.

Not protected

parameters

Parameter set

Next

Param.

Increase

value

Decrease

value

AHA

 35.0

spH

-15.5

0

Normal mode

Password

request

Parameter

(Program mode)

Correct password

inserted

2 s

5 s

Increase

value

Decrease

value

rp

2.5 

Reset parameters to default value

The instrument allows the reset of the parameters to values 
programmed in factory as default
To restore the default parameters value set value 

-48

 at 

r.p

 

password request  Therefore, to make the reset to the default 
parameters, enable the Password using the 

tPP

 parameter 

so that the 

r.p

 setting is requested, at this point insert 

-48

 

instead of the programmed access password.
Once confirmed the password with the 

/  key the display 

shows “

---

” for 2 s therefore the instrument resets all the 

parameters to factory default setting.

2.6 

Keyboard lock function

On the instrument it is possible to completely lock the keyboard.
This function is useful when the controller is in an accessible 
area and the changes must be avoided.
To activate the keyboard lock it is enough program the pa-
rameter 

tLo

 to a value different from 

oF

.

The 

tLo

 value is the keys inactivity time after which the key-

board will be automatically locked.
Therefore, pressing no buttons for the time set at 

tLo

, the 

instrument automatically disables the keys normal functions.

Содержание e33B

Страница 1: ...ration through stopping the compressor electric heating or hot gas cycle inversion The controller is equipped with special defrost optimization functions and with other functions that can be used to o...

Страница 2: ...Stand by mode this is the only lighted LED In programming mode while the parameter code is displayed the dot indicates the parameter protection level not protected lit up protected flashing and hidde...

Страница 3: ...ial test keeping it pressed for 5 s In this way it is possible to access all the parameters verify and modify the parameter tPP 2 4 Customized mode parameter programming parameters programming level T...

Страница 4: ...d rule must adopt all the necessary protective measures The instrument MUST NOT BE USED in dangerous environ ments flammable or explosive without adequate protections The instrument used with NTC 103A...

Страница 5: ...1 A Out 3 2 1 A 60730 EN UL 5 FUNCTIONS 5 1 ON Stand by function Once powered the instrument can assume 2 different conditions ON Means that the controller uses the control functions STAND BY Means t...

Страница 6: ...always closed 5 3 Measure and display configuration With parameter iuP it is possible to select the tempera ture engineering unit and the desired measure resolution C0 C 1 C1 C 0 1 F0 F 1 F1 F 0 1 The...

Страница 7: ...that is NO in normal operation then closed during the alarm AL To control an alarm that cannot be silenced through a contact that is NO in normal operation then closed during the alarm An To control a...

Страница 8: ...s automatic switching between the three Normal Eco Turbo modes described at the paragraph Operating modes The time protections described in the next paragraph PP1 PP2 PP3 always work on the ot configu...

Страница 9: ...a chines in which is required the maximum evaporator efficiency at each compressor cycle To enable automatic defrost at intervals after setting the ddC parameter as desired between rt ct or cS with th...

Страница 10: ...related to the EP probe under which defrosts are possible Therefore in the indicated modes if the temperature meas ured by the EP probe is higher than the one set at parameter dtS and also dtE defros...

Страница 11: ...emperature alarms Hi and Lo External alarm AL Door open oP The alarm functions acts on LED on the internal buzzer if present and configured by the obu parameter and on the desired output if configured...

Страница 12: ...The instrument can signal an alarm external to the instrument using the digital input setting iFi 4 or 5 The instrument signals the alarm turning ON the alarm LED and display ing AL label alternated...

Страница 13: ...f some instruments which need to have the same parameters con figuration or to keep a copy of the parameters settings of an instrument and allow its rapid retransmission The same device allows to conn...

Страница 14: ...ck 3 Open Door with Fan and Output Lock 4 External Alarm 5 External alarm with control output disabling 6 Normal Eco select 7 On Stand by select 8 Start a Turbo cycle 2 15 iti Digital Input Delay oF D...

Страница 15: ...n disabled 1 59 s 1 99 min 5 42 FtF Fan time deactivation with ot output compressor OFF oF Function disabled 1 59 s 1 99 min oF 43 FFL High temperature fan deactivation 99 9 999 C F 10 0 44 FLF Low te...

Страница 16: ...otu Time relative to auxiliary output oF Function disabled 1 59 s 1 99 min oF 67 tUF Key Function oF No function 1 Eco Mode direct selection turn OFF the showcase light if configured 2 Switch ON Swit...

Страница 17: ...faults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1 Electrical characteristics Power supply 230 VAC 115 VAC 12 VAC VDC 10...

Страница 18: ...C 103AT11 11 INSTRUMENT ORDERING CODE MODEL e33B Instrument with mechanical keyboard a POWER SUPPLY D 230 VAC C 115 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 H Out1 Relay SPST NO 16A AC1 for resistive loads R...

Страница 19: ...Ascon Tecnologic e33B OPERATING INSTRUCTIONS PAG 19...

Отзывы: