Ascon Tecnologic - e33B - OPERATING INSTRUCTIONS - PAG. 16
Parameter
Description
Range
Def.
Note
59
AdA
Temperature Alarms delay and
unlock display delay after defrost
oF
Function disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
1
60
AoA
Open Door Alarm Delay
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
3
61
oo1
OUT1 function
oF
No function;
ot
Temperature control (compressor);
dF
Defrost;
Fn
Fans;
Au
Auxiliary;
At/-t
Silenceable alarm;
AL/-L
Not silenceable Alarm;
An/-n
Stored Alarm;
on
ON when the instrument is ON;
HE
Heating (Neutral zone control)
L1
Showcase light with ECO function (ON with
SP
, OFF with
SPE
);
L2
Interior light (OFF with door closed, lit with door open).
ot
62
oo2
OUT2 function
Fn
63
oo3
OUT3 function
L1
64
obu
Buzzer function mode
oF
Function disabled;
1
Active for alarms only;
2
Active for key pressed only;
3
Active for alarms and key pressed.
3
65
oFo
Auxiliary output function
oF
Function disabled;
1
Control output
ot
delayed;
2
Manual activation by key.
oF
66
otu
Time relative to auxiliary output
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
67
tUF
/
Key Function
oF
No function;
1
Eco Mode direct selection
(+ turn OFF the showcase light, if configured);
2
Switch ON/Switch OFF (Stand-by) the controller.
1
68
tFb
/
Key Function
oF
No function;
1
Enable
key to control the light (
L1
and
Au
with
Fo
=
2
). 1
69
tLo
Keyboard lock function delay
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 30 (min).
oF
70
tEd
Set Point change procedure
0
Disabled;
1
Active Set Point Direct change between limits
SH
...
SE
;
2
Active Set Point Direct selection between SP1, SP2 and SP3
with
and
keys.
2
71
tPP
Password to Access Parameter set-up
oF
Function disabled;
001 ÷ 999.
oF
72
tdu
Filter to suppress the display of increasing temperature
variations lower than 0.1°
oF
Function disabled;
0.1 ÷ 20.0.
oF
73
tdd
Filter to suppress the display of decreasing temperature
variations lower than 0.1°
oF
Function disabled;
0.1 ÷ 20.0.
oF
74
ULU
Low mains alarm
oF
Function disabled;
9 ÷ 27 (V x 10).
oF
75
UHU
High Mains alarm
oF
Function disabled;
9 ÷ 27 (V x 10).
oF
76
UUd
Mains alamrs delay
oF
Function disabled;
-01 ÷ -59 (s) ÷ 01 ÷ 99 (min)
oF
77
UOU
Mains Voltage calibration
-30 ÷ 30 V
0