Ascon Tecnologic - e33B - OPERATING INSTRUCTIONS - PAG. 12

5.10.1  Temperature alarms

The temperature alarm works according to 

Pr1

 or 

AU

 probes 

measurement, the type of alarm set in the parameter 

AAy

 the 

alarm thresholds set in parameters 

AHA

 (maximum alarm) 

and 

ALA

 (minimum alarm) and the relative differential 

AAd

.

Through parameter 

AAy

 it is possible to set the alarm thresh-

olds 

AHA

 and 

ALA

 as absolute or relative to the active Set 

Point, must be related to 

Pr1

 or 

Au

 probes and if the message 

Hi

 (High alarm) and 

Lo

 (Low Alarm) are to be displayed (or 

not) at alarm intervention.
Depending on the desired alarm operating mode, parameter 

AAy

 can be set as:

1

 

Absolute alarms referred to probe 

Pr1

, displays 

Hi

/

Lo

;

2

 

Relative Alarms referred to probe 

Pr1

, displays 

Hi

/

Lo

;

3

 

Absolute alarms referred to probe 

Au

, displays 

Hi

/

Lo

;

4

 

Relative Alarms referred to probe 

Au

, displays 

Hi

/

Lo

;

5

 

Absolute alarm referred to probe 

Pr1

, displays no labels;

6

 

Relative alarm referred to probe 

Pr1

, displays no labels;

7

 

Absolute alarm referred to probe 

Au

, displays no labels;

8

 

Relative alarm referred to probe 

Au

, displays no labels.

Using some parameters it is also possible to delay the ena-
bling and the intervention of these alarms.
These parameters are:

APA

  Temperature alarm exclusion time on switching ON the 

instrument if the instrument is in alarm status when it 
is switched ON.  If the instrument is not in alarm status 
when it is switched on the time 

APA

 it is not considered.

AdA

 

Temperature alarm exclusion time at the end of de-
frost cycle (and, if programmed, after the draining) or 
after a continuous cycle.

AAt

  Temperature alarms delay activation time.  Tempera-

ture alarms are enabled at the end of the exclusion 
times and are activated after the 

AAt

 time when the 

temperature measured by the probe exceeds or goes 
below the respective maximum and minimum alarm 
thresholds.  The alarm thresholds are those set at 
parameters 

AHA

 and 

ALA

 when the alarms are set as 

absolute (

AAy

 = 

1

3

5

7

).

Temp.

AHA

AAd

time

AL

ALA

AAd

off

off

off

ON

ON

Hi

Lo

Pr1

or they assume the values [

SP

 + 

AHA

] and [

SP

 + 

ALA

if the alarms are relative (

AAy

 = 

2

4

6

8

).

AHA

SP

ALA

off

off

off

ON

ON

Hi

Lo

AL

AAd

AAd

Temp.

time

Pr1

The maximum and minimum temperature alarms can be disa-
bled by setting the related parameters 

AHA

 and 

ALA

 = 

oF

.

The temperature alarms are signalled lighting up the alarm 
LED ( ) and, if configured, also with the buzzer.

5.10.2  External alarm from digital input

The instrument can signal an alarm external to the instrument 
using the digital input setting 

iFi

 = 

4

 or 

5

.  The instrument 

signals the alarm turning 

ON

 the alarm LED ( ) and display-

ing 

AL

 label alternated to the variable set with parameter 

Ids

.

Mode 

iFi

 = 

4

 operates no action on the control output, while 

iFi

 = 

5

 deactivates the control output at digital input intervention.

5.10.3  Open door alarm

The instrument can signal the open door alarm coondition using 
the digital input setting 

iFi

 = 

1

2

 and 

3

.  As the digital input is 

activated, the instrument signals that the door is open showing 
on the display the 

oP

 label alternated to the variable set with 

parameter 

ids

.

After the delay set with parameter 

AoA

 the instrument signals 

the Open Door alarm with the configured devices (buzzer and/
or Output), lighting up the LED   while showing the 

oP

 label.  

At the open door alarm intervention are also re-activated the 
inhibited outputs (compressor).

5.10.4  Mains voltage alarms

The instrument can automatically disable the control outputs 
when the mains voltage, measured by the instrument through 
its power supply, is lower or higher than the values set at 
parameters:

ULU

  Low voltage alarm (expressed as V x 10);

UHU

  High voltage alarm (expressed as V x 10).

When the alarm triggers and after the delay programmed to 
the 

UUd

 parameter, the instrument disables the control out-

puts, signals the alarm by activating the configured device 
(output and/or buzzer) and shows 

HU

 (high voltage alarm), or 

LU

 (low voltage alarm) on the display alternated to the vari-

able set with 

dS

 parameter.

If the voltage measurement is not correct, it can be changed 
with an offset that can be set using the 

UOU

 parameter.

UHU

e.g. 250 V

ULU

e.g. 200 V

off

off

off

ON

ON

HU

LU

AL

10 V

10 V

Volt

time

V

5.11  Function of keys 

/  and  /

The 

/  key function can be defined using the 

tUF

 param-

eter to perform the following functions:

oF

 The key carries out no function;

Pressing the key for at least 1 s, is possible to enable/
disable the 

ECO

 operating mode.  Once the selection has 

been made, the display shows for about 1 s the active Set 
Point code (

SP1

SP2

SP3

 o 

Eco

) and its value.  When 

the instrument esits the 

ECO

 operating mode, it returns at 

the same operating mode it was using at 

ECO

 enabling;

Pressing the key for at least 1 s is possible to switch the 
instrument from 

ON

 to 

Stand-by

 state and vice-versa.

The  /

 key function can be defined using the 

tFb

 param-

eter to perform the following functions:

oF

 The key carries out no function;

Pressing the key for at least 1 s, is possible to enable/dis-
able the 

L1

 light output or the auxiliary output, if config-

ured as 

oFo

 = 

2

.

Содержание e33B

Страница 1: ...ration through stopping the compressor electric heating or hot gas cycle inversion The controller is equipped with special defrost optimization functions and with other functions that can be used to o...

Страница 2: ...Stand by mode this is the only lighted LED In programming mode while the parameter code is displayed the dot indicates the parameter protection level not protected lit up protected flashing and hidde...

Страница 3: ...ial test keeping it pressed for 5 s In this way it is possible to access all the parameters verify and modify the parameter tPP 2 4 Customized mode parameter programming parameters programming level T...

Страница 4: ...d rule must adopt all the necessary protective measures The instrument MUST NOT BE USED in dangerous environ ments flammable or explosive without adequate protections The instrument used with NTC 103A...

Страница 5: ...1 A Out 3 2 1 A 60730 EN UL 5 FUNCTIONS 5 1 ON Stand by function Once powered the instrument can assume 2 different conditions ON Means that the controller uses the control functions STAND BY Means t...

Страница 6: ...always closed 5 3 Measure and display configuration With parameter iuP it is possible to select the tempera ture engineering unit and the desired measure resolution C0 C 1 C1 C 0 1 F0 F 1 F1 F 0 1 The...

Страница 7: ...that is NO in normal operation then closed during the alarm AL To control an alarm that cannot be silenced through a contact that is NO in normal operation then closed during the alarm An To control a...

Страница 8: ...s automatic switching between the three Normal Eco Turbo modes described at the paragraph Operating modes The time protections described in the next paragraph PP1 PP2 PP3 always work on the ot configu...

Страница 9: ...a chines in which is required the maximum evaporator efficiency at each compressor cycle To enable automatic defrost at intervals after setting the ddC parameter as desired between rt ct or cS with th...

Страница 10: ...related to the EP probe under which defrosts are possible Therefore in the indicated modes if the temperature meas ured by the EP probe is higher than the one set at parameter dtS and also dtE defros...

Страница 11: ...emperature alarms Hi and Lo External alarm AL Door open oP The alarm functions acts on LED on the internal buzzer if present and configured by the obu parameter and on the desired output if configured...

Страница 12: ...The instrument can signal an alarm external to the instrument using the digital input setting iFi 4 or 5 The instrument signals the alarm turning ON the alarm LED and display ing AL label alternated...

Страница 13: ...f some instruments which need to have the same parameters con figuration or to keep a copy of the parameters settings of an instrument and allow its rapid retransmission The same device allows to conn...

Страница 14: ...ck 3 Open Door with Fan and Output Lock 4 External Alarm 5 External alarm with control output disabling 6 Normal Eco select 7 On Stand by select 8 Start a Turbo cycle 2 15 iti Digital Input Delay oF D...

Страница 15: ...n disabled 1 59 s 1 99 min 5 42 FtF Fan time deactivation with ot output compressor OFF oF Function disabled 1 59 s 1 99 min oF 43 FFL High temperature fan deactivation 99 9 999 C F 10 0 44 FLF Low te...

Страница 16: ...otu Time relative to auxiliary output oF Function disabled 1 59 s 1 99 min oF 67 tUF Key Function oF No function 1 Eco Mode direct selection turn OFF the showcase light if configured 2 Switch ON Swit...

Страница 17: ...faults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1 Electrical characteristics Power supply 230 VAC 115 VAC 12 VAC VDC 10...

Страница 18: ...C 103AT11 11 INSTRUMENT ORDERING CODE MODEL e33B Instrument with mechanical keyboard a POWER SUPPLY D 230 VAC C 115 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 H Out1 Relay SPST NO 16A AC1 for resistive loads R...

Страница 19: ...Ascon Tecnologic e33B OPERATING INSTRUCTIONS PAG 19...

Отзывы: