Ascon Tecnologic - e33B - OPERATING INSTRUCTIONS - PAG. 7

5.4 

Digital input configuration

The digital input function (available on 

terminal 12

 or instead 

of 

Pr3

 input if 

ip3

 = 

dg

) is defined using the 

iFi

 parameter 

and the action is delayed for the time programmed with pa-
rameter 

iti

.  The 

iFi

 parameter can be configured for the 

following functions:

Digital input not active;

Cell door opening with NO contact: at input closure (and 
after the 

iti

) the instrument displays alternately 

oP

 and 

the variable set at 

idS

 parameter.  With this mode of 

operation of the digital input activates also the time set 
with parameter 

AoA

 elapsed which the alarm is activated 

to warn that the door has been left open.  In addition, at 
door opening, the instrument returns to 

Normal

 operation 

if it was in 

Eco

 mode and the 

Eco

 mode activation was 

enabled through parameter 

iEt

;

Cell door opening with NO contact: Similar to 

iFi

 = 

1

 

but with evaporator fans stop.  In addition, at open door 
alarm intervention (

AoA

), the fans are restarted;

Cell door opening with compressor and fan outputs lock 
and NO contact: similar to 

iFi

 = 

2

 but with compressor 

and fans lock.  At open door alarm intervention (

AoA

both the fans and the compressor are re-activated.

External alarm signal with NO contact: at input closing 
(and after the 

iti

 time) the alarm is activated and the 

instrument alternately shows on the display: 

AL

 and the 

variable set with parameter 

idS

;

External alarm signal withall control outputs disabled and 
NO contact: at input closing (and after the 

iti

 time) all 

the control outputs are disabled, the alarm is activated 
and the instrument alternately shows on the display: 

AL

 

and the variable set with parameter 

idS

;

Normal

/

Eco

 mode selection with NO contact: at input clos-

ing (and after the 

iti

 time) the instrument switches to 

Eco

 operation mode.  Opening the digital input, the instru-

ment returns in 

Normal

 operation mode.

Instrument On/Off (stand-by) selection with NO contact: 
at input closing (and after the 

iti

 time) the instrument 

is switched ON while it is placed in Stand-by mode when 
the digital input is open;

Turbo

 cycle activation command with NO contact: at in-

put closing (and after the 

iti

 time) the instrument starts 

a Turbo cycle;

-1, -2, -3, etc.

 - Features identical to the above but obtained 

through a NC contact and a reversed logic operation.

5.5 

Outputs and buzzer configuration

The instrument outputs can be configured by the relative pa-
rameters 

oo1

oo2

 and 

oo3

.  The outputs can be configured 

for the following functions:

ot

 

To control the temperature control device (e.g. Compres-
sor).  To manage the cooling control device for neutral 
zone control or Cooling (

rHC

 = 

nr

);

df

 

To control the defrosting device;

Fn

 

To control the evaporator fans;

Au

 

To control the auxiliary device;

At

 

To control a silenceable alarm device through a contact 
that is NO in normal operation then closed during the 
alarm;

AL

 

To control an alarm that cannot be silenced through 
a contact that is NO in normal operation then closed 
during the alarm;

An

 

To control an alarm with a memory function through 
a contact that is NO in normal operation then closed  
during the alarm (see alarm memory);

-t

 

To control a silenceable alarm device through a con-
tact that is NC in normal operation then opened during 
the alarm;

-L

 

Control an alarm that cannot be silenced through a 
contact that is NC in normal operation  then opened 
during the alarm;

-n

 

To control an alarm with a memory function through 
a contact that is NC in normal operation then opened 
during the alarm;

on

 

To command a device that must be turned ON when 
the instrument is ON.  The output is therefore deac-
tivated when the instrument is not powered or is in 
standby mode.  This mode of operation can be used 
as a control of the shop window lighting, anti-fogging 
resistors or other utilities;

HE

 

To control a heating device in neutral zone (

rHC

 = 

nr

);

L1

 

Showcase light connected to 

Normal

/

Eco

 mode.  The 

output turns ON when the 

Normal

 mode is active while it 

is turned OFF when the 

Eco

 mode is active;

L2

 

Internal cell light.  The output is always OFF and only 
switches ON from a digital input  signal when it is con-
figured as door opening switch (

iFi

 = 

1

2

3

);

oF

 

Output disabled.

If one of the outputs is configured as auxiliary output (= 

Au

), 

its function is set by parameter 

oFo

 and its operation can be 

conditioned by the time set at parameter 

otu

.

oFo

 parameter can be configured for the following functions:

oF

 

Auxiliary output not active;

1

 

Temperature control output delayed with NO con-
tact: the auxiliary output is activated with a delay that 
can be set with parameter 

otu

 applied to the output 

configured as 

ot

.  The output is then turned OFF at 

the same time as the 

ot

 output is disabled.  This func-

tion mode can be used as a command for a second 
compressor or for all other working utilities according 
to the same ot output conditions, but which must be 
delayed after the start up of the compressor to avoid 
excess electricity absorption;

2

 

Activation by digital input.  The output is activated by 
a  digital input signal if correctly configured (

iFi

 = 

9

). 

These commands have a bi-stable (toggle) function (at 
first pression the output is activated, at the second is 
disabled).  The 

Aux

 output can be turned OFF auto-

matically after the time set at parameter 

otu

.

When 

otu

 = 

oF

 the output is activated and deactivated only 

manually, via the digital input.  Differently, the output, once 
activated, is turned OFF automatically after the 

otu

 time.  

This mode of operation can be used as a control of the shop 
window lighting, anti-fogging resistors or other utilities.
If present, the internal buzzer can be configured by param-
eter 

obu

 for the following functions:

oF

 

Buzzer always disabled;

1

 

The Buzzer sounds when an alarm is active;

2

 

The Buzzer sounds when a key pressed (no alarm);

3

 

The Buzzer sounds when a key pressed and when an 
alarm is active.

Содержание e33B

Страница 1: ...ration through stopping the compressor electric heating or hot gas cycle inversion The controller is equipped with special defrost optimization functions and with other functions that can be used to o...

Страница 2: ...Stand by mode this is the only lighted LED In programming mode while the parameter code is displayed the dot indicates the parameter protection level not protected lit up protected flashing and hidde...

Страница 3: ...ial test keeping it pressed for 5 s In this way it is possible to access all the parameters verify and modify the parameter tPP 2 4 Customized mode parameter programming parameters programming level T...

Страница 4: ...d rule must adopt all the necessary protective measures The instrument MUST NOT BE USED in dangerous environ ments flammable or explosive without adequate protections The instrument used with NTC 103A...

Страница 5: ...1 A Out 3 2 1 A 60730 EN UL 5 FUNCTIONS 5 1 ON Stand by function Once powered the instrument can assume 2 different conditions ON Means that the controller uses the control functions STAND BY Means t...

Страница 6: ...always closed 5 3 Measure and display configuration With parameter iuP it is possible to select the tempera ture engineering unit and the desired measure resolution C0 C 1 C1 C 0 1 F0 F 1 F1 F 0 1 The...

Страница 7: ...that is NO in normal operation then closed during the alarm AL To control an alarm that cannot be silenced through a contact that is NO in normal operation then closed during the alarm An To control a...

Страница 8: ...s automatic switching between the three Normal Eco Turbo modes described at the paragraph Operating modes The time protections described in the next paragraph PP1 PP2 PP3 always work on the ot configu...

Страница 9: ...a chines in which is required the maximum evaporator efficiency at each compressor cycle To enable automatic defrost at intervals after setting the ddC parameter as desired between rt ct or cS with th...

Страница 10: ...related to the EP probe under which defrosts are possible Therefore in the indicated modes if the temperature meas ured by the EP probe is higher than the one set at parameter dtS and also dtE defros...

Страница 11: ...emperature alarms Hi and Lo External alarm AL Door open oP The alarm functions acts on LED on the internal buzzer if present and configured by the obu parameter and on the desired output if configured...

Страница 12: ...The instrument can signal an alarm external to the instrument using the digital input setting iFi 4 or 5 The instrument signals the alarm turning ON the alarm LED and display ing AL label alternated...

Страница 13: ...f some instruments which need to have the same parameters con figuration or to keep a copy of the parameters settings of an instrument and allow its rapid retransmission The same device allows to conn...

Страница 14: ...ck 3 Open Door with Fan and Output Lock 4 External Alarm 5 External alarm with control output disabling 6 Normal Eco select 7 On Stand by select 8 Start a Turbo cycle 2 15 iti Digital Input Delay oF D...

Страница 15: ...n disabled 1 59 s 1 99 min 5 42 FtF Fan time deactivation with ot output compressor OFF oF Function disabled 1 59 s 1 99 min oF 43 FFL High temperature fan deactivation 99 9 999 C F 10 0 44 FLF Low te...

Страница 16: ...otu Time relative to auxiliary output oF Function disabled 1 59 s 1 99 min oF 67 tUF Key Function oF No function 1 Eco Mode direct selection turn OFF the showcase light if configured 2 Switch ON Swit...

Страница 17: ...faults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1 Electrical characteristics Power supply 230 VAC 115 VAC 12 VAC VDC 10...

Страница 18: ...C 103AT11 11 INSTRUMENT ORDERING CODE MODEL e33B Instrument with mechanical keyboard a POWER SUPPLY D 230 VAC C 115 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 H Out1 Relay SPST NO 16A AC1 for resistive loads R...

Страница 19: ...Ascon Tecnologic e33B OPERATING INSTRUCTIONS PAG 19...

Отзывы: