Ascon Tecnologic - e33B - OPERATING INSTRUCTIONS - PAG. 2

temperature control device

, the 

defroster

, the 

evaporator 

fans

 and a 

configurable auxiliary device

 (Light, Alarm, etc.).

The 

3 inputs for temperature probes

 can be used for the 

cell temperature control

, to measure the 

evaporator tem-

perature

 and/or other 

auxiliary temperatures

 (e.g. products 

temperature, condenser temperature, etc.).
The 

digital input

, alternative to the 

Pr3

 probe, can be config-

ured to 

perform various functions

 such as: cell gate signal, 

defrost commands, selection of a different set of temperature 
control, signaling of an external alarm, activation of a continu-
ous cycle, activation of the auxiliary output etc..

1.2 

Front panel pescription

e33B

P

U

trb

4

2

1

5

9

7

8

10

6

3

/

:

 Pressed for about 1 s enables the 

ECO

 function 

or turns the instrument ON/OFF (Stand-by).  The function 
selection is made with 

tUf

 parameter.  Pressed for 5 s 

together with the 

/  key, allows to access to the param-

eter programming mode.  Pressed for 5 s together with the 

/  key allows to access the variable display mode.  In 

programming mode it is used to return to normal operation;

/

:

 In normal mode, pressed an released allows to 

access the direct Set Point selection/change modality.  
Pressed for 5 s can be used to start/stop manual defrost 
cycle ( ).  In programming mode and in variable display 
mode is used to select the parameters and to increase 
the value to be set.  In programming mode can be used 
together with 

/  key to change parameters level.  

When the keyboard is locked, the keys 

/  and 

/  

used together (hold pressed for 5 s), unlock the keyboard.

/  

turbo

:

 In normal mode, pressed an released al-

lows to access the direct Set Point selection/change 
modality.  Pressed for 5 s can be used to start/stop a 
control cycle with “

turbo

” modality (

)

.  In programming 

mode and in variable display mode is used to select the 
parameters and to increase the value to be set.

/ :

 Pressed for about 1 s enables/disables the output 

selected as “

Light

”.  The function selection is made with 

tfb

 

parameter.  Pressed for 5 s together with the 

/  key, 

allows to access to the parameter programming mode.  
In programming mode is used to enter in parameters 
edit mode and confirm the entered values.  In program-
ming mode 

 can be used together with the 

/  key 

to change the programming level of the parameters.  
Pressed together with the 

/  key for 5 s allows the 

keyboard unlock.

5  LED dp/Stand-by:

 During the normal operation is the 

decimal point, when the instrument is placed in Stand-
by mode, this is the only lighted LED.  In programming 
mode, while the parameter code is displayed, the dot 
indicates the parameter protection level: 

not protected 

(lit up), 

protected

 (flashing) and 

hidden

 (turned OFF).

6  LED 

: Indicates the output status (compressor or 

temperature control device) when the instrument 
is programmed for 

cooling operation

ON

 (lit up), 

OFF

 (turned OFF) or 

inhibited

 (flashing).

7  LED  :

 Indicates the output status (compressor or temper-

ature control device) when the instrument is programmed 
for 

heating operation

ON

 (lit), 

OFF

 (turned OFF) or 

inhib-

ited

 (flashing).

8  LED  :

 Indicates the 

alarm status

ON

 (lit), 

OFF

 (turned OFF) or 

silenced or stored

 (flashing).

9  LED  :

 Indicates that the 

defrost

 is 

in progress

 (on) or 

drainage time in progress

 (flashing).

10  LED  :

 Indicates 

fan

 output status 

ON

 (on), 

OFF

 (off) 

or 

inhibited

 (flashing).

2.  PROGRAMMING

2.1 

Fast Normal Set Point Programming

The instrument allows, through the 

tEd

 parameter, to man-

age the selection of the regulation Set point according to two 
distinct  modes.
Setting 

tEd

 =

1

 the instrument allows the 

SP1 

Set Point set-

ting inside the limits inserted with 

SPH

 and 

SPE

 parameters.

Using this method, press and release the 

 or 

 key, the 

controller anwers showing the 

SP1

 active, at this point, using 

the 

 and 

 keys is possible to change the SP2 value to 

the desired one.  Once the desired value has been selected, 
press the 

/

 

key or wait 10 s after which the instrument 

makes the new set Point value active and the display returns 
to the normal operating mode.

Max. = 

spE

 value

ECO SET (e.g. 10°)

Min. = 

spH

 value

Turbo SET (e.g. -10°)

Increase

value

Decrease

value

-2.0

tEd

 = 1 mode

Set Point programming

Setting 

tEd

 = 

2

, the controller allows to select which of the 3 

pre-set Set Points (

SP1

SP2

SP3

) is to be set to active.  In 

this mode, pressing and releasing the ss / dd key the instru-
ment shows the active Set Point (

SP1

SP2

SP3

) alternatedto 

its value, pressing the 

/

 keys again it will be possible to 

select which one of the three is to be activated.  Once the de-
sired Set Point has been activated, press the 

/

 

key or wait 

10 s after which the instrument makes the selected Set Point 
active and the display returns to the normal operating mode.

sp1

 (e.g. 4.0°)

sp2

 (e.g. 2.0°)

Increase

selection

Decrease

selection

sp2

tEd

 = 2 mode

Set Point selection

sp3

 (e.g. 0.0°)

The use of the device with 

tEd

 = 

2

 is the most practical and 

simple for the end user who, with the operations illustrated be-
low, can easily select, as the active, one among the 4/5 preset 
Set Point temperatures (

SPE

SP1

SP2

 , 

SP3

 and 

SPH

).

-2.0

Press and 

hold for 1s

Press and 

release

(e.g. 4.0°)

eco 10.0

(e.g. -5.0°)

trb -5.0

(e.g. 4.0°)

sp1

4..0

(e.g. 2.0°)

sp2

2.0

(e.g. 0.0°)

sp3

0.0

or

Press and 

hold for 5s

Содержание e33B

Страница 1: ...ration through stopping the compressor electric heating or hot gas cycle inversion The controller is equipped with special defrost optimization functions and with other functions that can be used to o...

Страница 2: ...Stand by mode this is the only lighted LED In programming mode while the parameter code is displayed the dot indicates the parameter protection level not protected lit up protected flashing and hidde...

Страница 3: ...ial test keeping it pressed for 5 s In this way it is possible to access all the parameters verify and modify the parameter tPP 2 4 Customized mode parameter programming parameters programming level T...

Страница 4: ...d rule must adopt all the necessary protective measures The instrument MUST NOT BE USED in dangerous environ ments flammable or explosive without adequate protections The instrument used with NTC 103A...

Страница 5: ...1 A Out 3 2 1 A 60730 EN UL 5 FUNCTIONS 5 1 ON Stand by function Once powered the instrument can assume 2 different conditions ON Means that the controller uses the control functions STAND BY Means t...

Страница 6: ...always closed 5 3 Measure and display configuration With parameter iuP it is possible to select the tempera ture engineering unit and the desired measure resolution C0 C 1 C1 C 0 1 F0 F 1 F1 F 0 1 The...

Страница 7: ...that is NO in normal operation then closed during the alarm AL To control an alarm that cannot be silenced through a contact that is NO in normal operation then closed during the alarm An To control a...

Страница 8: ...s automatic switching between the three Normal Eco Turbo modes described at the paragraph Operating modes The time protections described in the next paragraph PP1 PP2 PP3 always work on the ot configu...

Страница 9: ...a chines in which is required the maximum evaporator efficiency at each compressor cycle To enable automatic defrost at intervals after setting the ddC parameter as desired between rt ct or cS with th...

Страница 10: ...related to the EP probe under which defrosts are possible Therefore in the indicated modes if the temperature meas ured by the EP probe is higher than the one set at parameter dtS and also dtE defros...

Страница 11: ...emperature alarms Hi and Lo External alarm AL Door open oP The alarm functions acts on LED on the internal buzzer if present and configured by the obu parameter and on the desired output if configured...

Страница 12: ...The instrument can signal an alarm external to the instrument using the digital input setting iFi 4 or 5 The instrument signals the alarm turning ON the alarm LED and display ing AL label alternated...

Страница 13: ...f some instruments which need to have the same parameters con figuration or to keep a copy of the parameters settings of an instrument and allow its rapid retransmission The same device allows to conn...

Страница 14: ...ck 3 Open Door with Fan and Output Lock 4 External Alarm 5 External alarm with control output disabling 6 Normal Eco select 7 On Stand by select 8 Start a Turbo cycle 2 15 iti Digital Input Delay oF D...

Страница 15: ...n disabled 1 59 s 1 99 min 5 42 FtF Fan time deactivation with ot output compressor OFF oF Function disabled 1 59 s 1 99 min oF 43 FFL High temperature fan deactivation 99 9 999 C F 10 0 44 FLF Low te...

Страница 16: ...otu Time relative to auxiliary output oF Function disabled 1 59 s 1 99 min oF 67 tUF Key Function oF No function 1 Eco Mode direct selection turn OFF the showcase light if configured 2 Switch ON Swit...

Страница 17: ...faults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1 Electrical characteristics Power supply 230 VAC 115 VAC 12 VAC VDC 10...

Страница 18: ...C 103AT11 11 INSTRUMENT ORDERING CODE MODEL e33B Instrument with mechanical keyboard a POWER SUPPLY D 230 VAC C 115 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 H Out1 Relay SPST NO 16A AC1 for resistive loads R...