Ascon Tecnologic - e33B - OPERATING INSTRUCTIONS - PAG. 14

7.  PROGRAMMABLE PARAMETERS TABLE

Here below is a description of all the parameters available on the instrument.  Some of them may not be present, either due 
to the fact they depend on the type of instrument or because they are automatically disabled as unnecessary.

Parameter

Description

Range

Def.

Note

SPH

Turbo Set Point (or indep. Heating Set Point, HC mode) -99.9 ÷ SPE

-5.0

SPE

Set Point Eco

S.PH ÷ 999

10.0

SP1

Set Point 1

SPH ÷ SPE

4.0

SP2

Set Point 2

SPH ÷ SPE

2.0

SP3

Set Point 3

SPH ÷ SPE

0.0

iuP

Unit of measurement and resolution (decimal point)

C0

  °C, resolution 1°;

F0

  °F, resolution 1°;

C1

  °C, resolution 0.1°;

F1

  °F, resolution 0.1°.

C1

iFt

Measurement filter

oF

  Not used;

0.1 ÷ 20.0 s

2.0

iC1

Pr1 Probe Calibration

-30.0 ÷ +30.0°C/°F

0.0

iC2

Pr2 Probe Calibration

-30.0 ÷ +30.0°C/°F

0.0

10 

iC3

Pr3 Probe Calibration

-30.0 ÷ +30.0°C/°F

0.0

11 

iCU

Display offset

-30.0 ÷ +30.0°C/°F

0.0

12 

iP2

Input Pr2 usage

oF

 Unused;

EP

  Evaporator probe;

Au

  Auxliary probe;

dG

  Digital Input.

dG

13 

iP3

Input Pr3 usage

dG

14 

iFi

Function and logic functioning of the Digital Input  

(adding the “-” minus sign the logic is inverted)

0

  No function;

1

  Open Door;

2

  Open Door with Fan Lock;

3

  Open Door with Fan and Output Lock;

4

  External Alarm;

5

  External alarm with control output disabling;

6

  Normal/Eco select;

7

  On/Stand by select;

8

  Start a Turbo cycle.

2

15 

iti

Digital Input Delay

oF

 Disabled;

-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).

oF

16 

iEt

Eco Mode activation delay at Door closed

oF

 Disabled;

-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).

02

17 

itt

Max. time functioning in Eco Mode

oF

 Disabled;

-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).

oF

18 

idS

Variable normally displayed

oF

  Display not lit;

P1

  Probe Pr1 measure;

P2

  Probe Pr2 measure;

P3

  Probe Pr3 measure;

Ec

 Measure 

Pr1

 in Normal mode + 

ECO

 label when in ECO mode;

SP

  Active Set Point.

P1

19 

rd

Differential (Hysteresis)

0.0 ÷ 30.0°C/°F

2.0

20 

rEd

Differential (Hysteresis) in ECO mode

0.0 ÷ 30.0°C/°F

4.0

21 

rHd

Differential (Hysteresis) in Turbo mode or Heating in 

HC mode

0.0 ÷ 30.0°C/°F

2.0

22 

rt1

Output activation time for Pr1 probe error

oF

 Disabled;

-1 ÷ -59 (s) 1 ÷ 99 (min).

oF

23 

rt2

Output deactivation time for Pr1 probe error

oF

 Disabled;

-1 ÷ -59 (s) 1 ÷ 99 (min).

oF

24 

rHC

Output operating mode

H

 Heating;

C

 Cooling;

nr

  Neutral zone;

HC

  Neutral Zone with indep. Set Point;

C3

  Cooling with3 autom. switch modes.

C

25 

rtC

Lengh of Turbo cycle

oF

  Function disabled;

-1 ÷ -59 (min) 1 ÷ 99 (h).

1

26 

dtE

Defrost stop temperature

-99.9 ÷ +999°C/°F

8.0

27 

dtS

Defrost enable temperature

-99.9 ÷ +999°C/°F

10.0

28 

dtF

Defrost start temperature

-99.9 ÷ +999°C/°F

-99.9

29 

dSt

Delay start Defrost by 

dtF

 start temperature

oF

  Function disabled;

-1 ÷ -59 (s) ÷ 1 ÷ 99 (min) 

1

Содержание e33B

Страница 1: ...ration through stopping the compressor electric heating or hot gas cycle inversion The controller is equipped with special defrost optimization functions and with other functions that can be used to o...

Страница 2: ...Stand by mode this is the only lighted LED In programming mode while the parameter code is displayed the dot indicates the parameter protection level not protected lit up protected flashing and hidde...

Страница 3: ...ial test keeping it pressed for 5 s In this way it is possible to access all the parameters verify and modify the parameter tPP 2 4 Customized mode parameter programming parameters programming level T...

Страница 4: ...d rule must adopt all the necessary protective measures The instrument MUST NOT BE USED in dangerous environ ments flammable or explosive without adequate protections The instrument used with NTC 103A...

Страница 5: ...1 A Out 3 2 1 A 60730 EN UL 5 FUNCTIONS 5 1 ON Stand by function Once powered the instrument can assume 2 different conditions ON Means that the controller uses the control functions STAND BY Means t...

Страница 6: ...always closed 5 3 Measure and display configuration With parameter iuP it is possible to select the tempera ture engineering unit and the desired measure resolution C0 C 1 C1 C 0 1 F0 F 1 F1 F 0 1 The...

Страница 7: ...that is NO in normal operation then closed during the alarm AL To control an alarm that cannot be silenced through a contact that is NO in normal operation then closed during the alarm An To control a...

Страница 8: ...s automatic switching between the three Normal Eco Turbo modes described at the paragraph Operating modes The time protections described in the next paragraph PP1 PP2 PP3 always work on the ot configu...

Страница 9: ...a chines in which is required the maximum evaporator efficiency at each compressor cycle To enable automatic defrost at intervals after setting the ddC parameter as desired between rt ct or cS with th...

Страница 10: ...related to the EP probe under which defrosts are possible Therefore in the indicated modes if the temperature meas ured by the EP probe is higher than the one set at parameter dtS and also dtE defros...

Страница 11: ...emperature alarms Hi and Lo External alarm AL Door open oP The alarm functions acts on LED on the internal buzzer if present and configured by the obu parameter and on the desired output if configured...

Страница 12: ...The instrument can signal an alarm external to the instrument using the digital input setting iFi 4 or 5 The instrument signals the alarm turning ON the alarm LED and display ing AL label alternated...

Страница 13: ...f some instruments which need to have the same parameters con figuration or to keep a copy of the parameters settings of an instrument and allow its rapid retransmission The same device allows to conn...

Страница 14: ...ck 3 Open Door with Fan and Output Lock 4 External Alarm 5 External alarm with control output disabling 6 Normal Eco select 7 On Stand by select 8 Start a Turbo cycle 2 15 iti Digital Input Delay oF D...

Страница 15: ...n disabled 1 59 s 1 99 min 5 42 FtF Fan time deactivation with ot output compressor OFF oF Function disabled 1 59 s 1 99 min oF 43 FFL High temperature fan deactivation 99 9 999 C F 10 0 44 FLF Low te...

Страница 16: ...otu Time relative to auxiliary output oF Function disabled 1 59 s 1 99 min oF 67 tUF Key Function oF No function 1 Eco Mode direct selection turn OFF the showcase light if configured 2 Switch ON Swit...

Страница 17: ...faults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1 Electrical characteristics Power supply 230 VAC 115 VAC 12 VAC VDC 10...

Страница 18: ...C 103AT11 11 INSTRUMENT ORDERING CODE MODEL e33B Instrument with mechanical keyboard a POWER SUPPLY D 230 VAC C 115 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 H Out1 Relay SPST NO 16A AC1 for resistive loads R...

Страница 19: ...Ascon Tecnologic e33B OPERATING INSTRUCTIONS PAG 19...

Отзывы: