![Asco 230 Series Скачать руководство пользователя страница 7](http://html.mh-extra.com/html/asco/230-series/230-series_user-manual_2981100007.webp)
Chapter 1 Overview 3
ASCO Series 230 Automatic Transfer Switch C2000 Intelligent Controller User Manual
Electromagnetic immunity performance parameters of C2000 controller:
Table 1-5 Electromagnetic Immunity Performance Parameters
Item
Requirements & Criterion
Standard
Surge Immunity
Criterion: A
AC inputs Port
:±
2KV
DC port
:±
800V
Signal Port
:±
2kV
EN 61000-4-5
Immunity to Electrical Fast Transient
Level 3
Criterion: A
Power Port: 2kV
Signal Port: 1kV
EN 61000-4-4
Immunity to Electrostatic Discharge
Criterion: A
Contact discharge: 6kV
Air discharge : 8kV
IEC61000-4-2
Immunity to Radiated Electric Fields
Criterion: A
10V/m, 80MHz - 1GHz
IEC61000-4-3
Immunity to Continuous Conducted
Interference
Criterion: A
Power Port: 10V
Signal Port: 10V, 150 kHz - 80MHz
EN 61000-4-6
Certification requirements of C2000 controller:
Table 1-6 Certification Requirements
Certification Categories
Standard
CE
EN60947-6-1
IEC
IEC60947-6-1
1.4 Accessory Information
Please check and make sure you have received all the accessory items in Table 1-7. These are included as standard
with your C2000 Controller.
Table 1-7 Accessories included with Standard C2000 Controller
Standard Accessory Description
Model / Specification
Part Number
Quantity
Comments
Controller Corner Snaps
63201405
4
Grounding Cable
LTSC2000SLW03
04110370
1
Length: 200mm
Series 230 C2000 Intelligent Controller User Manual
31012586
1
Note: Controller Power & Signal Cables are included with the ASCO Series 230 Transfer Switch Unit packaging.
Содержание 230 Series
Страница 2: ......
Страница 4: ......
Страница 22: ...18 Chapter 3 Operation Series 230 Automatic Transfer Switch C2000 Intelligent Controller User Manual ...