20 Chapter 3 Operation
Series 230 Automatic Transfer Switch C2000 Intelligent Controller User Manual
Control Settings
2. SETTINGS
Control
2.1 Rated Vol
380V
2.2 Rated Freq
50Hz
2.3 Input Typ
L1L2L3/L1L2L3N
2.4 Control Mode
S1 Prior
2.5 Device Sel
Series 230-2
ENTER
UP
DOWN
2.6 Over Vol Set
NO
2.7 Ph Rot Order
NO
2.8 UnBal Set
NO
Parameter
Default
value
Setting range
Description
Rated Voltage
380V
220V / 230V / 240V /
380V / 400V / 415V
Choose line-to-neutral voltage for 2 pole.
Choose line-to-line voltage for 3 pole or 4
pole.
Rated
Frequency
50Hz
50Hz / 60Hz
Rated frequency.
Input Type
L1L2L3/L1L
2L3N
L1L2L3/L1L2L3N
LN/L1L2/L1L2N
Use”
LN/L1L2/L1L2N”for 2 pole, Single
Phase
. Use “L1L2L3/L1L2L3N”for 3 pole or
4 pole, Three Phase
Control Mode
Source I
Priority
Source I Priority, No
Source Priority,
Remote Control, and
Manual
Choose the control mode
Device
Selection
Series
230-2
Series 230-1
Series 230-2
Series 230-3
Series 230-1: Three-position with central
position protection
Series 230-2: Three-position without central
position protection
Series 230-3: Two-Position
Over Vol Set
NO
No
YES
NO: Over Voltage Disable
YES: Over Voltage Enable
Ph Rot Order
NO
NO
ABC
CBA
NO: phase rotation monitor disable
ABC: positive-sequenc e as reference
CBA: negative-sequence as reference
UnBal Set
NO
NO
8%
15%
25%
NO:
unbalanced monitor disable
8%/15%/25%: the unbalanced Drop Out