Chapter 3 Operation 23
ASCO Series 230 Automatic Transfer Switch C2000 Intelligent Controller User Manual
Key Pad to Directly Operate Switch
Parameter
Default value
Setting range
Remarks
Switch Action
X->O
X->O
X->I
X->II
X->O: The switch transfers to Position O
X->I: The switch transfers to Position I
X->II: The switch transfers to Position II
Note: This menu is valid only when operating the
switch directly with the key pad.
Generator
Control
Generator
startup
Generator
startup
Generator
stop
Output the generator control signal
Note: This menu is valid only when operating
the switch directly with the key pad.
Generator Auto
Startup
Refer to “Automatic Generator Test”
System information
Parameter
Default
value
Description
System
Version
For information only, cannot be changed.
Program
Version
For information only, cannot be changed.
Number of
Transfers
00000
/00000
It indicates the number of times the switch has transfered under the
control of the controller.
Press “Enter” key to enter the setup, where you can clear the parameter.
Press “Up” and “Down” keys to clear the number and reset to 0000.
Press “Esc” key to exit the setup or invalidate this setting.
Press “Enter” key again to save the current setting value and exit.
format
:
Total number of transfers : 00000 to 99999
The successful number of transfers: 00000 to 99999
Automatic Generator Test
Parameter
Default
value
Description
7.3 Generator Auto
Test Start Menu
NOTE: The automatic test function setting for the generator
will not affect the switch transfer's normal operation.
Whether to start the
test automatically
YES
YES: Activate automatic test
NO: Disable automatic test and exit
Day Used for Startup
Time
15
Enter the startup day for automatic test, e.g. XX day of each
month.
Startup Time
00:00
Enter the startup hour for automatic test. NOTE: HH:MM,
Using 24 Hour Method
Running Time
00:00
Amount of time required to run the generator test.
NOTE: HH:MM, Using 24 Hour Method