2 Chapter 1 Overview
Series 230 Automatic Transfer Switch C2000 Intelligent Controller User Manual
RS485 with MODBUS communications protocol
Up to 100 event log recording capability. Log is saved in the event of a power loss.
1.3 Technical Parameters
Application condition requirements of C2000 Controller as shown in Table 1-1.
Table 1-1 Application Conditions of C2000
Requirement
Condition
Standards
Temperature
Operating Temperature
-
20
℃~+
60
℃
IEC61800-1
Storage Temperature
-
40
℃~+
70
℃
Temperature Change
5
℃
/min
Humidity
95
%
, No condensation
IEC60721-3-3 3K3
Altitude
2000m or less
IEC60721-3-3 3K3
Vibration
5~9
,
9~200Hz
,
3.5mm
,
10m/s2
,
5
sweep cycles,1oct/min
IEC60721-3-3 3M4
Shock
Sinusoidal
,
15g,6ms
,
3 times/direction
IEC60721-3-3 3M4
Technical parameters of C2000 controller as shown in Table 1-2
Table 1-2 Technical Parameters of C2000 controller
Item
Parameter
Rated Operating Voltage
(
Ue
)
2 Pole
:
220Vac (L-N) / 230Vac (L-N) / 240Vac (L-N)
3 Pole / 4 Pole
:
380Vac (L-L) / 400Vac (L-L) / 415Vac (L-L)
Operating Voltage Range
Ue = 220V / 230V / 240V / 380V / 400V
(
0.7
~
1.2
)
x Ue
Ue = 415V
(
0.7
~
1.15
)
x Ue
Rated Operation Frequency
50Hz / 60Hz
Rated Insulation Impulse Withstand Voltage
6kV
Protection Class of Enclosure
IP20
Pollution Degree
3
Overvoltage Class
Distribution level, Industral conditions.
Lightning Tolerability Level
Impulse voltage wavform: 10 / 700µs, 5kV 10 times
Impulse voltage waveform: 8 / 20
µ
s, 20kA 1 time
Detectable range and accuracy of C2000 controller are shown in Table 1-3.
Table 1-3 Detect Range and Detect Accuracy
Signal to be Detected
Accuracy
Detectable Range
Remarks
AC Voltage
±2
%
80Vac ~ 480Vac
Share the sampling port with the power input port.
AC Frequency
±1
%
45Hz ~ 65Hz
Electromagnetic interference performance parameters of C2000 controller:
Table 1-4 Electromagnetic Interference Performance Parameters
Item
Requirements
Standard
Conducted Disturbance Emission
Class A
EN 55022
Radiation Distubance Emission
Class A
EN 55022
Harmonic Current Emission
Class A
EN61000-3-2
Voltage Fluctuations and Flicker
Class A
EN61000-3-3
Содержание 230 Series
Страница 2: ......
Страница 4: ......
Страница 22: ...18 Chapter 3 Operation Series 230 Automatic Transfer Switch C2000 Intelligent Controller User Manual ...