Electromagnetic Flowmeter M-910
54
Operation manual
11 Technical data
Nominal size
DN10 to DN800
Nominal pressure
PN10 to PN25 (depending on nominal size)
Flow range
0.1 to 10 m/s (0.01 to 5000 l/s) / (0.03 to 18000 m3/h)
Accuracy
•
0.5 % (0.5 to 10 m/s) of reading value
•
1 % (0.1 to 0.5 m/s) of reading value
Maximum media temperature
70
o
C (158
o
F) for rubber liner
130
o
C (266
o
F) for PTFE liner in remote version
Minimum electrical conductivity
≥
5
µ
S / cm
Ambient temperature
-20 to 60
°
C (-4 to 140
°
F)
Power supply
•
115/230V ( +10%, -20%), 50/60Hz, auto selectable (M910-Vxx0x)
•
12V DC (+20%, -10%), 12V 50/60Hz (+10%, -10%)
(M910-Vxx1x)
•
24V DC (+20%, -10%), 24V 50/60Hz (+10%, -10%)
(M910-Vxx2x)
•
48V DC (+20%, -10%), 48V 50/60Hz (+10%, -10%)
(M910-Vxx3x)
Power consumption
10 VA
Liner
•
hard rubber
•
soft rubber
•
PTFE
Electrodes
•
CrNi (stainless) steel 1.4571
•
Hastelloy C276
•
Tantalum
Measuring tube
Stainless steel 1.4201, dimensions according to DIN 17457
Flange
Steel 1.0402 or higher
Dimensions according to DIN 2501 (BS 4504) or ANSI B16.5
Protection category
•
Compact version: IP67, optionally IP68
•
Remote version: sensor IP68, converter IP65
Outputs
•
Frequency 0 to 12 kHz with programmable flowrate and function
•
Pulse 0 to 50 Hz with programmable volume, function and pulse width
•
Relay contacts 100V/0.5A with programmable function
•
Current loop 4 to 20 mA with programmable flowrate and function
Input
PLC digital input with programmable function
Communication
•
RS485
•
RS232
Displayed values
•
Flowrate (m3/h, l/s, US.Gal/min, user)
•
Volume (m3, l, US.Gal, user)
•
Positive, total, negative and auxiliary (clearable, daily) volume
Control
•
Keyboard
•
Magnetic pointer
•
RS232 and RS485