Electromagnetic flowmeter M910
Operation manual
11
3.2 Electrical connection
Only a competent person may connect the flowmeter to the mains power supply.
The flowmeter can be connected to the power supply with either a fixed power cable or with a flying lead cable and
plug. Cable entries on the electronic unit can be used for flexible electrical cables. Cables with a diameter between
8 and 10 mm must be used to keep protection IP67. It is not recommended to use rigid metal or plastic conduits.
If you use a cable and plug
it
is recommended that the cable has a cross-section of 3 x 1.5mm
2
and with a minimum
length of 1 m.
In the case of a fixed connection an independent power switch or circuit breaker should be located close to the
flowmeter. Cable cross-section as above.
3.2.1 Compact version
To connect the compact version to the power supply the following procedure should be used.
•
Unscrew the back cover using the special wrench (standard part of delivery).
•
Connect the earth wire (yellow-green colour) to the central grounding point inside the case. The end of earth
wire must be hooked (app. 3 mm) and fixed to the earth screw.
•
Connect Live and Neutral power cables to the power line terminal clamps with labels 14 (L-wire, brown
terminal colour) and 13 (N-wire, blue terminal colour).
•
Screw on the back cover.
•
Switch on the power supply.
Note:
Be careful to avoid following problems during electrical installation:
•
Do not cross or loop cables inside electronic unit.
•
Use separate cable entries for power supply and signal wires.
GND central grounding point
L line wire
N line wire