5. System description
The system is started with the AUTOMATIC -button, after which the ignition
pages open. If the flame detection system detects a flame in the burner head,
the burner switches to effect mode. After the ignition phase, the burner
switches to effect mode, during which the effect of the burner is adjusted
according to the required heating power. The automatic system attempts to
maintain the boiler water temperature at the set level. If a high level of heating
is not required, but the boiler water temperature increases excessively, the
burner will activate the upkeeping mode.
The burner uses the upkeeping mode to maintain ember in the burner head.
When the boiler water temperature decreases, the burner returns to the effect
mode. The user can stop storage operation and empty the burner screw by
NOT IN USE
(STOP
mode)
- pumps are running
- flue gas fan is on
AUTOMATIC
IGNITION 1
1. Fanning
2. Funnel filling
3. Ignition load
4. Ignition
No flame
Flame
IGNITION 2
Constant voltage
EFFECT MODE
21-100% power
UPKEEPING
Ember
maintenance
Boiler temperature > Setting
+hysteresis
Boiler temperature < S0.5 x hysteresis
Flame
ALARM
For example,
Emergency stop or
flame detection.
SHUTDOWN
- by the user
- Buffer tank
control (automatic
start-up)