17.5.
Ash screws
Figure 22. ASH SCREWS settings.
Setting
Factory
setting
Setting
frequency
Function
Running time
240s
0-600s
Ash removal duration. Ash screw 1 is
controlled with pulses while Ash screw 2
auger is controlled continuously.
Pause ratio
(Effect/s)
7,200
0-32,000
Ash screw interval relation to the burner
effect. For example, if the burner runs
for 2h (7,200s) at 100% power, the ash
screw are activated.
Ash screws are run according to the burner effect. At higher burner effect
levels the pause is shorter than at lower burner effect levels. The
Running
time
-setting determines the running duration of the ash screws. The
Pause
ratio
determines the ash removal pause length at 100% burner effect level.
For example, if the burner runs at 50% effect, the pause is twice as long.