v2.00
Ariterm Oy
21.5.2013
18
Then, the burner screw feeds fuel to the
burner head for the duration of the set
time. There should be an appropriate
amount of fuel in the burner head.
Hot air gun running
time at step 2
30s
0-360s
Hot air gun operation time after flame
detection (ignition phase 2).
The automatic ignition is initialised either by the user or automatically by the
accumulator upper temperature sensor. The storage auger automatically fills
the funnel and the boiler is ventilated before ignition. When the funnel is full,
the burne screw runs for the duration of the
Burner screw filling time (long)
-setting, feeding an appropriate amount of fuel to the burner head. NOTE! If
the system is halted by an alarm while the burner screw is full of fuel, the user
can select a short filling time during ignition. During the short filling, the screw
will feed the burner head for the duration of the
Burner screw filling time
(short)
-setting.
The hot air gun and combustion air fans operate for the duration of the
Ignition step 1
-setting. If the flame detection detects a flame, the burner will
activate the
Ignition 2
-phase. The optical flame detection sensor must detect
a flame during the duration of the
Flame delay
-setting in order to activate the
flame data. If the flame detection fails to detect a flame during the
Ignition
step 1
-time setting, the fans and ignition stop and the
Alarm! automatic
ignition
alarm is displayed.
During the
Ignition 2
-phase, the burner runs at a power level configured in
the
Burner screw
-setting for the duration of the
Ignition step 2
-setting. After
this the burner automatically activates the effect mode. If the flame disappears
during the
Ignition 2
-phase, the
Alarm! Automatic ignition
-alarm is
displayed.
Power settings for the burner screw and the combustion air fans during the
ignition phases are set in the
BURNER SCREW/PRIMARY
FAN/SECONDARY FAN
-setting pages.
The hot air gun can be activated by pressing the IGNITION UP->EFFECT -
button once the burner switches from
Upkeep
to
Effect
mode.