The temperature control features an outdoor temperature sensor, supply
water temperature sensor and a 0-10V shunt valve control. The supply water
temperature can be fixed (OUT TEMPERATURE CONTROL NOT IN USE -
button) or set according to outdoor temperature. The heating curve can be
defined with four points, which the system uses to calculate the supply water
temperature according to outdoor temperature.
Figure 25. Trend page
This also allows the user to adjust the enhancement and Ti values of the
control. The
Gain (P)
and
Integration time
(
Ti)
-settings (integration) control
the adjustment speed and accuracy.
Out
temperature
-20°C
-5°C
5°C
20°C
Water
temperature
35°C
30°C
25°C
20°C