The system can be equipped with a pulse extinguishing system for preventing
back fires by humidifying fuel with water when the auger surface temperature
increases. There are two humidification temperatures. Pulse extinguishing
utilises a Pt100 sensor, which measures the burner screw temperature, and a
magnetic valve, which controls the water supply to the burner screw.
NOTE! Water extinguishing system cannot be used with pellets.
When the burner screw surface temperature exceeds the
Level 1
temperature
-setting, the magnetic valve is controlled according to the
Level
1 Extinguishing pulse
and the
Level1 Pause time
-settings. Pulses are
continued until the temperature falls below the setting. If the temperature
keeps rising, the system will switch to the faster level 2 pulses. If the burner
screw surface temperature exceeds the
Temp. limit (back fire)
-setting, the
burner will react similarly to when a back fire thermostat is set off.
SMS alarms can be activated with the LEVEL 1/2 ALARM NOT IN USE -
buttons.
17.4 Residual oxygen-control
Figure 20. O2-CONTROL settings.
Setting
Factory
setting
Setting
frequency
Function
O2 set point
8.0%
6.0-15.0% Residual oxygen target value
Measured O2
True value
0-25%
Residual oxygen true value
O2 alarm limit
4.0%
0-8.0%
Residual oxygen alarm limit.
O2-control
minimum
-5.0%
0..-50%
Secondary fan maximum power
reduction.
O2-control
maximum
15.0%
0-50%
Secondary fan maximum power
increase.