v2.00
Ariterm Oy
21.5.2013
39
Setting
Factory
setting
Setting
frequency
Function
Upper temperature
True
value
0-100°C
Buffer tank upper temperature.
Lower temperature
True
value
0-100°C
Buffer tank lower temperature.
Pump start
temperature
80°C
0-100°C
Boiler water temperature at which the
load pump starts.
Pump stop
temperature
78°C
0-50°C
Boiler water temperature at which the
load pump stops.
Burner start
temperature
60°C
0-100°C
The burner is activated when the Buffer
tank upper temperature falls below the
temperature setting.
Burner stop
temperature
80 C
0-100°C
When the accumulator lower
temperature exceeds the setting, the
burner will shut down.
Upper temperature
max. temperature
90°C
0-110°C
Buffer tank maximum upper
temperature.
Temperature sensor
scaling min.
-10°C
-
150...150°
C
Buffer tank sensor scaling. NOTE!
Requires Maintenance level password.
Temperature sensor
scaling max
150°C
-
150...150°
C
Buffer tank sensor scaling. NOTE!
Requires Maintenance level password.
Buffer tank control features the Buffer tank upper and lower temperature
sensors and load pump control. The burner must be equipped with automatic
ignition. Buffer tank usage can be activated from the
OPTIONS
-menu. The
burner will begin ignition once the system is set to
Automatic
-mode. When
using the system for the first time you should perform a manual ignition, so
that the
AUTOMATIC IGNITION
-settings can be done accurately.
You can enable the BUFFER TANK CONTROL -button during the ignition.
After the ignition phase, the burner switches to effect mode. When the
temperature of the boiler water exceeds the
Pump start temperature
-setting,
the load pump starts loading the buffer tank.
When the buffer tank lower temperature exceeds the
Burner stop
temperature
-setting, the burner begins shutting down. The storage auger
stops and the burner screw is emptied, until the flame detection no longer
detects a flame. When no flame is detected, the burner is in standby mode.
The load pump stops when the boiler water temperature falls below the
Pump
stop temperature
-setting. When the buffer tank upper temperature falls
below the
Burner start temperature
-setting, automatic ignition and new
loading start.