Figure. 5.4.10. - 101. If current transformer starpoints are pointing towards each other or away from each other, “Add” differential
calculation mode is used.
Figure. 5.4.10. - 102. If current transformer starpoints are pointing towards the same direction, “Subtract” differential calculation
mode is used.
Differential function has 2 separate stages inbuilt which of the non restraint uses only these formulas as
comparison base. For the restraint characteristics also so called “Bias” calculation is made per each
phase to adjust the sensitivity of the differential stage up to the measured currents.
For the bias calculation also two separate formulas are available.
Average mode (sensitive biasing):
AQ-T216
Instruction manual
Version: 2.00
129
© Arcteq Relays Ltd