Reset
Reset time
Typically <10 ms
Reset ratio
97 %
9.3. Tests and environmental
Electrical environment compatibility
Table. 9.3. - 184. Disturbance tests
All tests
CE approved and tested according to EN 60255-26
Emissions
Conducted emissions:
EN 60255-26 Ch. 5.2, CISPR 22
150kHz - 30 MHz
Radiated emissions:
EN 60255-26 Ch. 5.1, CISPR 11
30 - 1 000 MHz
Immunity
Electrostatic discharge (ESD):
EN 60255-26, IEC 61000-4-2
Air discharge 15 kV
Contact discharge 8 kV
Fast transients (EFT):
EN 60255-26, IEC 61000-4-4
Power supply input 4kV, 5/50ns, 5kHz
Other inputs and outputs 4kV, 5/50ns, 5kHz
Surge:
EN 60255-26, IEC 61000-4-5
Between wires 2 kV / 1.2/50µs
Between wire and earth 4 kV / 1.2/50µs
Radiated RF electromagnetic eld:
EN 60255-26, IEC 61000-4-3
f = 80….1000 MHz 10V /m
Conducted RF eld:
EN 60255-26, IEC 61000-4-6
f = 150 kHz….80 MHz 10V
Table. 9.3. - 185. Voltage tests
Dielectric voltage test
EN 60255-27, IEC 60255-5, EN 60255-1
2 kV, 50Hz, 1min
Impulse voltage test:
EN 60255-27, IEC 60255-5
5 kV, 1.2/50us, 0.5J
Physical environment compatibility
Table. 9.3. - 186. Mechanical tests
Vibration test:
EN 60255-1, EN 60255-27, IEC 60255-21-1
2 ... 13.2 Hz ±3.5mm
13.2 ... 100Hz, ±1.0g
Shock and bump test
EN 60255-1,EN 60255-27, IEC 60255-21-2
20g, 1000 bumps/dir.
AQ-T216
Instruction manual
Version: 2.00
281
© Arcteq Relays Ltd
Содержание AQ 200 Series
Страница 1: ...AQ T216 Transformer protection IED Instruction manual ...
Страница 243: ...Figure 7 1 162 AQ T216 variant with binary input modules AQ T216 Instruction manual Version 2 00 Arcteq Relays Ltd 242 ...
Страница 264: ...Figure 8 11 184 Panel cut out and spacing of the IED AQ T216 Instruction manual Version 2 00 263 Arcteq Relays Ltd ...
Страница 284: ...10 Ordering information AQ T216 Instruction manual Version 2 00 283 Arcteq Relays Ltd ...
Страница 285: ...AQ T216 Instruction manual Version 2 00 Arcteq Relays Ltd 284 ...