Figure. 5.4.11. - 117. RTD alarm set up.
In the motor module RTD alarm function can be set to monitor previously set RTD channels
measurement data. A single channel can be set to have several alarms by selecting the channel to
multiple sensor inputs. In each sensor setting can be selected the monitored module and channel. Also
the monitoring and alarm setting units (C/F) can be selected here. Alarms can be enabled either “over”
or “under” and the setting value is input as degrees. In the RTD alarm function are 12 sensor inputs
available. For the alarm to be active channel measurement must be valid. Channel measurement can
be invalid if the communication is not working or sensor is broken.
Settings
Table. 5.4.11. - 87. Settings of the RTD function for channel x/12.
Name
Range
Step
Default
Description
Sx enable
0:No
1:Yes
-
0:No
Enable / Disable selection of the sensor measurements and alarms
Sx module
0:ModuleA
1:ModuleB
2:ModuleC
-
0:ModuleA Selection of the measurement module
AQ-T216
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
160