![Arcteq AQ 200 Series Скачать руководство пользователя страница 201](http://html1.mh-extra.com/html/arcteq/aq-200-series/aq-200-series_instruction-manual_2964929201.webp)
Table. 5.5.5. - 113. Event codes of the PCS function
Event Number
Event channel
Event block name
Event Code
Description
384
6
PCS
0
Switch1 On
385
6
PCS
1
Switch1 Off
386
6
PCS
2
Switch2 On
387
6
PCS
3
Switch2 Off
388
6
PCS
4
Switch3 On
389
6
PCS
5
Switch3 Off
390
6
PCS
6
Switch4 On
391
6
PCS
7
Switch4 Off
392
6
PCS
8
Switch5 On
393
6
PCS
9
Switch5 Off
5.6. Monitoring functions
5.6.1. Current transformer supervision (CTS)
Current transformer supervision (CTS) function is meant to be used for monitoring the CTs, wirings in
between of the IED and IED CT inputs in case of malfunction or wire breaks. Open CT circuit can
generate dangerously high voltages into the CT secondary side as well as cause not intended
activation of current balance monitoring functions.
CTS function constantly monitors phase current instant values as well as key calculated magnitudes of
the phase currents. Also, residual current circuit can be monitored if the residual current is measured
from dedicated residual current CT. Residual circuit monitoring can be enabled or disabled by user
selection.
Blocking signal and setting group selection controls the operating characteristics of the function during
normal operation.
Outputs of the function are CTS alarm and Blocked signals. Setting parameters are static inputs for the
function which are changed only by user input in the setup phase of the function. CTS function utilizes
total of eight separate setting groups which can be selected from one common source. Also, the
operating mode of the CTS can be changed by setting group selection.
The operational logic consists of input magnitude processing, threshold comparator, block signal
check, time delay characteristics and output processing.
For the CTS function alarm activation following conditions has to be met simultaneously:
None of the three phase currents is over the set Iset Highlimit setting
At least one of the three phase currents are over the Iset Lowlimit setting
At least one of the three phase currents are under the Iset Lowlimit setting
Three phase current calculated Min/Max ratio is under the Iset ratio setting
Negative sequence / Positive sequence ratio is over the I2/I1 ratio setting
Calculated (IL1+IL2+IL3+I0) difference is over the Isum difference setting (optional)
Above mentioned condition is met until the set TCTS time
AQ-T216
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
200
Содержание AQ 200 Series
Страница 1: ...AQ T216 Transformer protection IED Instruction manual ...
Страница 243: ...Figure 7 1 162 AQ T216 variant with binary input modules AQ T216 Instruction manual Version 2 00 Arcteq Relays Ltd 242 ...
Страница 264: ...Figure 8 11 184 Panel cut out and spacing of the IED AQ T216 Instruction manual Version 2 00 263 Arcteq Relays Ltd ...
Страница 284: ...10 Ordering information AQ T216 Instruction manual Version 2 00 283 Arcteq Relays Ltd ...
Страница 285: ...AQ T216 Instruction manual Version 2 00 Arcteq Relays Ltd 284 ...