TT>
Condition
0:Normal
1:Alarm1 On
2:Alarm2 On
3:Inhibit On
4:Trip On
5:Blocked
TOLT function operating condition at the moment considering binary IO signal status. When the
status is “Normal” no outputs are controlled.
Thermal
status
0:Light / No
load
1:High
overload
2:Overloading
3:Load
normal
TOLT function thermal image status. When the measured current is below 1 % of nominal status
“Light / No load” will be shown, when the measured current is below trip limit status “Load
normal” will be shown, when the measured current is over pick-up limit but under 2 xIn status
“Overloading” will be shown and when measured current is over 2 xIn status “High overload” will
be shown.
Table. 5.4.9. - 75. Measurements
Name
Range
Description / values
Currents
0:Primary A
1:Secondary A
2:Per unit
Active phase current measurement from IL1(A), IL2(B) and IL3(C) phases in given
scalings.
Thermal
Image
0:Thermal image
calc.
TT> Trip expect mode: No trip expected / Trip expected
TT> time to 100% theta: Time to reach 100% thermal cap
TT> reference T curr.: Reference / pick-up value (IEQ)
TT> Active meas curr.: Measured max TRMS current at the moment
TT> T est.with act curr.: Estimate of used thermal capacity with current at the moment
TT> T at the moment: Thermal capacity used at the moment
1: Temp estimates
TT> Used k for amb.temp: Ambient correction factor at the moment
TT> Max.Temp.Rise All: Maximum temperature rise allowed
TT> Temp.Rise atm: Calculated temperature rise at the moment
TT> Hot Spot estimate: Estimated hot spot temperature including the ambient
temperature
TT> Hot Spot Max. All: Maximum allowed temperature for the object
2: Timing status
TT> Trip delay remaining: Time to reach 100% theta
TT> Trip time to rel.: Time to theta to reach under trip limit when cooling
TT> Alarm 1 time to rel.: Time to theta to reach under Alarm 1 limit when cooling
TT> Alarm 2 time to rel.: Time to theta to reach under Alarm 2 limit when cooling
TT> Inhibit time to rel.: Time to theta to reach under Inhibit limit when cooling
Table. 5.4.9. - 76. Counters
Name
Description / values
Alarm1 inits
Times the TOLT function has activated the Alarm 1 output
Alarm2 inits
Times the TOLT function has activated the Alarm 2 output
Restart inhibits
Times the TOLT function has activated the Restart inhibit output
Trips
Times the TOLT function has tripped
Trips Blocked
Times the TOLT function trips has been blocked
Events and registers
The TOLT function generates events and registers from the status changes of the Trip activated and
blocked signals. To main event buffer is possible to select status “On” or “Off” messages.
In the function is available 12 last registers where the triggering event of the function (Trip activated or
blocked) is recorded with time stamp and process data values.
Table. 5.4.9. - 77. Event codes of TOLT function.
Event Number
Event channel
Event block name
Event Code
Description
4672
73
TOLT1
0
Alarm1 On
4673
73
TOLT1
1
Alarm1 Off
AQ-T216
Instruction manual
Version: 2.00
121
© Arcteq Relays Ltd
Содержание AQ 200 Series
Страница 1: ...AQ T216 Transformer protection IED Instruction manual ...
Страница 243: ...Figure 7 1 162 AQ T216 variant with binary input modules AQ T216 Instruction manual Version 2 00 Arcteq Relays Ltd 242 ...
Страница 264: ...Figure 8 11 184 Panel cut out and spacing of the IED AQ T216 Instruction manual Version 2 00 263 Arcteq Relays Ltd ...
Страница 284: ...10 Ordering information AQ T216 Instruction manual Version 2 00 283 Arcteq Relays Ltd ...
Страница 285: ...AQ T216 Instruction manual Version 2 00 Arcteq Relays Ltd 284 ...