Figure. 5.6.1. - 141. System in case when there is no wiring fault and heavy unbalance.
If any of the phases is over the Iset Highlimit the operation of the CTS is not activated. This behavior is
applied in short circuit and earth faults also if the fault current exceeds the Iset high setting.
Figure. 5.6.1. - 142. System in case of low current and heavy unbalance.
If all of the measured phases magnitudes are below the Iset Lowlimit setting the CTS is not activated
even the unbalance and other conditions are met.
By adjusting the Iset Highlimit and Iset Lowlimit setting parameters according to the application normal
behavior, the operation of the CTS can be set to very sensitive for broken circuit/conductor faults.
AQ-T216
Instruction manual
Version: 2.00
205
© Arcteq Relays Ltd