HV side nominal
current(sec)
0.01…250.00A
0.01A
0.00A
Info
Calculated transformer HV side secondary
current.
HV CT nom to TR nom
factor
0.01…250.00p.u.
0.01p.u.
0.00A
Info
Calculated transformer HV side nominal to
CT primary rate.
LV side nominal
current(pri)
0.01…50000.00A
0.01A
0.00A
Info
Calculated transformer LV side primary
current.
LV side nominal
current(sec)
0.01…250.00A
0.01A
0.00A
Info
Calculated transformer LV side secondary
current.
LV CT nom to TR nom
factor
0.01…250.00p.u.
0.01p.u.
0.00p.u.
Info
Calculated transformer LV side nominal to CT
primary rate.
Transformer nom
impedance
0.01…250.00ohm
0.01ohm 0.00ohm Info
Calculated transformer nominal impedance.
Transformer nom Zk
ohm
0.01…250.00ohm
0.01ohm 0.00ohm Info
Calculated transformer nominal short circuit
impedance.
Transformer nom SC
inductance
0.001…
250.000uH
0.01uH
0.000uH Info
Calculated transformer nominal short circuit
inductance.
Transformer ratio
0.01…250.00
0.01
0.00
Info
Calculated transformer ratio. (HV/LV)
LV side max 3ph SC
curr
0.001…
500.000kA
0.001kA
0.000kA
Info
Calculated maximum three phase short
circuit current in the LV poles of the trafo.
LV side 3ph SC to HV
side
0.001…
500.000kA
0.001kA
0.000kA
Info
Calculated max three phase short circuit
current in LV side shows to HV side.
LV side max 2ph SC
curr
0.001…
500.000kA
0.001kA
0.000kA
Info
Calculated maximum two phase short circuit
current in the LV poles of the trafo.
LV side 2ph SC to HV
side
0.001...500.000kA 0.001kA
0.000kA
Info
Calculated max two phase short circuit
current in LV side shows to HV side.
Table. 5.4.8. - 66. Output signals of the TRF function
Name
Range Step Default
Description
No/Light
load
0:Not
active
1:Active
1
0
Signal is active, when the TRF function detects current below “No load current”.
This signal presents situation when there is very light load or only one or neither
side of trafo is energized.
HV side
inrush
detected
0:Not
active
1:Active
1
0
Signal is active, when the detected current rises over the “High overcurrent” limit
in the HV side.
LV side
inrush
detected
0:Not
active
1:Active
1
0
Signal is active, when the detected current rises over the “High overcurrent” limit
in the LV side.
Load
normal
0:Not
active
1:Active
1
0
Signal is active when the measured current is below nominal and over no load
limit current.
Overloading
0:Not
active
1:Active
1
0
Signal is active when the measured current is in between nominal and high
overcurrent limits.
HVY
Overloading
0:Not
active
1:Active
1
0
Signal is active when the measured current is over high overcurrent limit.
Events
TRF function generates events from detected transformer energizing status. From changes of the
events also data register is available.
Table. 5.4.8. - 67. Event codes of the TRF function
Event Number
Event channel
Event block name
Event Code
Description
AQ-T216
Instruction manual
Version: 2.00
113
© Arcteq Relays Ltd
Содержание AQ 200 Series
Страница 1: ...AQ T216 Transformer protection IED Instruction manual ...
Страница 243: ...Figure 7 1 162 AQ T216 variant with binary input modules AQ T216 Instruction manual Version 2 00 Arcteq Relays Ltd 242 ...
Страница 264: ...Figure 8 11 184 Panel cut out and spacing of the IED AQ T216 Instruction manual Version 2 00 263 Arcteq Relays Ltd ...
Страница 284: ...10 Ordering information AQ T216 Instruction manual Version 2 00 283 Arcteq Relays Ltd ...
Страница 285: ...AQ T216 Instruction manual Version 2 00 Arcteq Relays Ltd 284 ...