Figure. 4.4. - 12. Protection stage related events are masked on and off individually under
Events
→
Event mask
.
Events are masked off as default. It is possible to activate desired events by masking them |x|. Only
masked events appear to event list. Events cannot be cleared.
Stage activation
Figure. 4.4. - 13. Stage activation sub-menu.
Activation
of different protection stages is done in
Stage activation
–sub menu. Each protection
stage and supporting function is disabled as standard.
Activated menus will appear below the stage speci c sub-menu for example I> appears below
Current –module, U< appears below Voltage-module etc.
AQ-T216
Instruction manual
Version: 2.00
17
© Arcteq Relays Ltd