Measured input values
Function block uses analog current measurement values. Function block utilizes calculated positive
and negative sequence currents. In broken conductor mode (I2/I1) also the phase currents RMS
values are used for the minimum current check. Zero sequence and the component sequence angles
are used for the fault registering and for fault analysis processing. -20ms averaged value of the
selected magnitude is used for pre-fault data registering.
Table. 5.4.4. - 41. Analogic magnitudes used by the CUB function.
Signal
Description
Time base
I1
Positive sequence current magnitude
5 ms
I2
Negative sequence current magnitude
5 ms
IZ
Zero sequence current magnitude
5 ms
I1 ANG
Positive sequence current angle
5 ms
I2 ANG
Negative sequence current angle
5 ms
IZ ANG
Zero sequence current angle
5 ms
IL1RMS
Phase L1 (A) measured RMS current
5 ms
IL2RMS
Phase L2 (B) measured RMS current
5 ms
IL3RMS
Phase L3 (C) measured RMS current
5 ms
Selection of the used AI channel is made with a setting parameter. In all possible input channel
variations pre-fault condition is presented with 20 ms averaged history value from -20 ms of Start or
Trip event.
General settings
The following general settings de ne the general behavior of the function. These settings are static i.e.
it is not possible change them with setting group switching.
Name
Description
Range Step Default
Meas side
De nes which current measurement module is used by the function. Visible if unit
has more than one current measurement module.
1:Side1
2:Side2
-
1:Side1
Measured
magnitude
De nes if the ratio between positive and negative sequence currents are
supervised or if only negative sequence is used in unbalance detection.
1:I2pu
2:I2/I1
-
1:I2pu
Pick-up characteristics
Pick-up of the CUB function is controlled by I2set or I2/I1set setting parameters, which de ne the
maximum allowed measured negative sequence current or negative/positive sequence current ratio
before action from the function. The function constantly calculates the ratio in between of the Iset and
measured magnitude (Im). Reset ratio of 97 % is inbuilt in the function and is always related to the
Ixset value. The reset ratio is common for both modes.
Table. 5.4.4. - 42. Pick-up characteristics setting
Name
Description
Range
Step
Default
I2set
Pick-up setting for I2 mode
0.01…40.00xIn
0.01xIn
0.2xIn
I2/I1set
Pick-up setting for I2/I1 mode
1…200%
0.01%
20%
AQ-T216
Instruction manual
Version: 2.00
81
© Arcteq Relays Ltd
Содержание AQ 200 Series
Страница 1: ...AQ T216 Transformer protection IED Instruction manual ...
Страница 243: ...Figure 7 1 162 AQ T216 variant with binary input modules AQ T216 Instruction manual Version 2 00 Arcteq Relays Ltd 242 ...
Страница 264: ...Figure 8 11 184 Panel cut out and spacing of the IED AQ T216 Instruction manual Version 2 00 263 Arcteq Relays Ltd ...
Страница 284: ...10 Ordering information AQ T216 Instruction manual Version 2 00 283 Arcteq Relays Ltd ...
Страница 285: ...AQ T216 Instruction manual Version 2 00 Arcteq Relays Ltd 284 ...