Add 4 to each of the numbers above to disable the Lead/Lag indication
on the Power Factor Display.
A.3.42
Range, Set (SRG)
Command:
rng#,ch#SRG
Used to set the analog input range. After the range is set, puts the selected
channel into Range-Hold Mode. Use the ch#RRH command to release
Range-Hold. The approximate input ranges are as follows:
Rng#
AC Voltage
AC Current
DC Voltage
0
0 – 3.5
0 – .09
0 – 5
1
3 – 7
0.8 – 0.18
4.2 – 10
2
6 – 14
0.16 – 0.37
8.5 – 20
3
12 – 28
0.32 – 0.75
17 – 40
4
24 – 56
0.64 – 1.49
34 – 80
5
48 – 112
1.28 – 2.98
68 – 160
6
96 – 224
2.56 – 5.97
135.8 – 320
7
192 – 448
5.12 – 11.9
271.5 – 640
8
384 – 750
10.24 – 20.0
543 – 1000
ch#
To Select
1
Channel 1
2
Channel 2
A.3.43
Scale Factors, Set or Return (SSC)
Command:
in#,m#,p#,s/r#SSC
Set or return calibration factors to be applied to each input function,
such as for CT or PT corrections. Scale factors consist of a magnitude
correction, which is a ratio (or p/u) number; and a phase angle, in degrees.
Multiplies the measured result by the magnitude correction and adds the
phase angle.
in# – specifies the input signal configuration, as follows:
120
Содержание 931A
Страница 6: ...vi ...
Страница 12: ...xii ...
Страница 14: ...xiv ...
Страница 16: ...xvi ...
Страница 52: ...SOURCE LOAD B A C N Figure 3 12 3 Phase 4 Wire 3 Element Connections 36 ...
Страница 90: ...Iout I1 V1 V2 V3 I2 I3 Figure 3 17 3 Phase 4 Wire 3 Element Transducer Test 74 ...
Страница 114: ...98 ...
Страница 120: ...104 ...
Страница 142: ...126 ...