FST 500 Manual
- Page 83 -
Pr.89 Transmission Speed (Baud rate)
Factory Setting: 01
Settings
00 4800 bps
01 9600 bps
02 19200 bps
03 38400 bps
★
This parameter sets the transmission speed for communication on the RS-485 serial port
Pr.90 Transmission Fault Treatment
Factory Setting: 03
Settings
00 Warn and Continue Operating
01 Warn and RAMP to Stop
02 Warn and COAST to Stop
03 Keep Operation without Warning
Pr.91 Time Out Detection
Factory Setting: 0.0
Settings 0.1 to 120.0 sec
0.0disable
★
This parameter is used for ASCII mode. When the over-time detection is enabled, the separation
between characters cannot exceed 500 ms.
Pr.92 Communication Protocol
Factory Setting: 00
Settings
00 Modbus ASCII mode, <7,N,2>
01 Modbus ASCII mode, <7,E,1>
02 Modbus ASCII mode, <7,O,1>
03 Modbus RTU mode, <8,N,2>
04 Modbus RTU mode, <8,E,1>
05 Modbus RTU mode, <8,O,1>
1. Computer Control
●
Each drive has a built-in RS-485 serial interface, marked (RJ-11 Jack) on the control terminal block,
whose pins are defined as shown:
Содержание FST-500 Series
Страница 8: ...FST 500 Manual Page 8 1 1 3 External Parts and Labels...
Страница 9: ...FST 500 Manual Page 9 1 1 4 Remove instructions...
Страница 17: ...FST 500 Manual Page 17...
Страница 22: ...FST 500 Manual Page 22 2 4 Control Terminal Wiring Factory Settings...
Страница 27: ...FST 500 Manual Page 27 3 1 2 How to Operate the Digital Keypad LC M02E...
Страница 28: ...FST 500 Manual Page 28 3 1 3 LC M02E Reference Table for the 7 segment LED Display of the Digital Keypad...
Страница 49: ...FST 500 Manual Page 49 Commonly used V F Setting 1 General Purpose...
Страница 87: ...FST 500 Manual Page 87 ASCII mode Command message Response message RTU mode Command message Response message...
Страница 110: ...FST 500 Manual Page 110 Chapter 5 Troubleshooting 5 1 Over Current OC...
Страница 111: ...FST 500 Manual Page 111 5 2 Ground Fault 5 3 Over Voltage OV...
Страница 112: ...FST 500 Manual Page 112 5 4 Low Voltage Lv...
Страница 113: ...FST 500 Manual Page 113 5 5 Over Heat OH1 5 6 Overload...
Страница 114: ...FST 500 Manual Page 114 5 7 Keypad Display is Abnormal 5 8 Phase Loss PHL...
Страница 115: ...FST 500 Manual Page 115 5 9 Motor cannot Run...
Страница 116: ...FST 500 Manual Page 116 5 10 Motor Speed cannot be Changed...
Страница 134: ...FST 500 Manual Page 134...
Страница 135: ...FST 500 Manual Page 135...
Страница 144: ...FST 500 Manual Page 144 EMI Filter RF022M21BA RF075M43BA EMI Filter 16TDT1W4S Used on 0 5 3 HP 230V Three Phase Models...
Страница 145: ...FST 500 Manual Page 145 EMI Filter 40TDS4W4B Used on 5 7 5 HP 230V Three Phase Models...