FST 500 Manual
- Page 72 -
Pr.55
※
Slip Compensation
Settings 0.00 to 10.00 Factory Setting: 0.00
★
This parameter can be used to compensate motor slip. Although no linear, it typically adds 6Hz for a
setting of 10 if Pr.03=60 Hz. When the output current of the AC drive is greater than the motor
no-load current (Pr.53), the AC drive will adjust its output frequency according to this parameter.
Pr.56 Reserved
Pr.57 Rated Current Display of the AC motor drive
Settings Read Only Factory Setting: ##.#
◆
Pr.57 displays the rated current of the AC motor drive. By reading this parameter the user can
check if the AC motor drive is correct. See Pr.80 for details.
Pr.58 Electronic Thermal Overload Relay Selection
Factory Setting: 02
Settings 00 Standard Motor (self cool motor)
01 Inverter Motor (auxiliary cool fan on motor)
02 Inactive
★
This function is used to limit the output power of the AC drive when powering a “self-cooled
motor” at low speed.
Pr.59 Electronic Thermal Motor Overload Unit: 1 second
Settings 30 to 300sec Factory Setting: 60
◆
The parameter determines the time required to activate the I2t electronic thermal motor overload
protection. The graph below shows I2t curves at 150% output power for 1 minute.
Содержание FST-500 Series
Страница 8: ...FST 500 Manual Page 8 1 1 3 External Parts and Labels...
Страница 9: ...FST 500 Manual Page 9 1 1 4 Remove instructions...
Страница 17: ...FST 500 Manual Page 17...
Страница 22: ...FST 500 Manual Page 22 2 4 Control Terminal Wiring Factory Settings...
Страница 27: ...FST 500 Manual Page 27 3 1 2 How to Operate the Digital Keypad LC M02E...
Страница 28: ...FST 500 Manual Page 28 3 1 3 LC M02E Reference Table for the 7 segment LED Display of the Digital Keypad...
Страница 49: ...FST 500 Manual Page 49 Commonly used V F Setting 1 General Purpose...
Страница 87: ...FST 500 Manual Page 87 ASCII mode Command message Response message RTU mode Command message Response message...
Страница 110: ...FST 500 Manual Page 110 Chapter 5 Troubleshooting 5 1 Over Current OC...
Страница 111: ...FST 500 Manual Page 111 5 2 Ground Fault 5 3 Over Voltage OV...
Страница 112: ...FST 500 Manual Page 112 5 4 Low Voltage Lv...
Страница 113: ...FST 500 Manual Page 113 5 5 Over Heat OH1 5 6 Overload...
Страница 114: ...FST 500 Manual Page 114 5 7 Keypad Display is Abnormal 5 8 Phase Loss PHL...
Страница 115: ...FST 500 Manual Page 115 5 9 Motor cannot Run...
Страница 116: ...FST 500 Manual Page 116 5 10 Motor Speed cannot be Changed...
Страница 134: ...FST 500 Manual Page 134...
Страница 135: ...FST 500 Manual Page 135...
Страница 144: ...FST 500 Manual Page 144 EMI Filter RF022M21BA RF075M43BA EMI Filter 16TDT1W4S Used on 0 5 3 HP 230V Three Phase Models...
Страница 145: ...FST 500 Manual Page 145 EMI Filter 40TDS4W4B Used on 5 7 5 HP 230V Three Phase Models...