FST 500 Manual
- Page 77 -
17 External Base-Block (bb)
18 Overload 2 (oL2)
19 Auto Adjustable accel/decel failure (cFA)
20 Software protection code (codE)
Pr.76 Parameter Lock and Configuration
Factory Setting: 00
Settings
00 All parameters can be set/read
01 All parameters are read-only
02-08 Reserved
09 Resets all parameters to 50Hz factory defaults
10 Resets all parameters to 60Hz factory defaults
★
This parameter allows the user to reset the drive to factory settings.
Pr.77 Time for Auto Reset the Restart Times after Fault Unit: 0.1 second
Settings 0.1 to 6000.0 sec Factory Setting: 60.0
◆
If there is no fault in the period of this setting, it will reset the rest restart times that used after fault
to the setting of restart times.
Pr.78 PLC Operation Mode
Factory Setting: 00
Settings
00 Disable PLC operation
01 Execute one program cycle
02 Continuously execute program cycles
03 Execute one program cycle step by step (separated by “STOP”)
04 Continuously execute program cycles step by step (separated by “STOP”)
◆
This M drive can be programmed to execute a sequence of operations named “PLC mode”. The
PLC program can be used in lieu of any external controls, relays or switches. The AC drive will
change speeds and directions according to the user‟s desired programming. This parameter
selects the PLC operation mode for the drive. Please review the following examples:
Example 1 (Pr.78 =01)
: Execute one cycle of the PLC program. Its relative parameter settings are:
1. Pr.17 to Pr.23:
1st to 7th step speed (sets the frequency for each step speed)
2. Pr.38 to Pr.42:
Multi-Function Input Terminals (program one multi-function terminal for PLC
auto-operation (16).
3. Pr.45 to Pr.46:
Multi-Function Output Terminals : program a Multi-Function Output Terminal for PLC
operation indication (09), one cycle in PLC auto mode (10) or PLC operation fulfillment attainment
(11).
Содержание FST-500 Series
Страница 8: ...FST 500 Manual Page 8 1 1 3 External Parts and Labels...
Страница 9: ...FST 500 Manual Page 9 1 1 4 Remove instructions...
Страница 17: ...FST 500 Manual Page 17...
Страница 22: ...FST 500 Manual Page 22 2 4 Control Terminal Wiring Factory Settings...
Страница 27: ...FST 500 Manual Page 27 3 1 2 How to Operate the Digital Keypad LC M02E...
Страница 28: ...FST 500 Manual Page 28 3 1 3 LC M02E Reference Table for the 7 segment LED Display of the Digital Keypad...
Страница 49: ...FST 500 Manual Page 49 Commonly used V F Setting 1 General Purpose...
Страница 87: ...FST 500 Manual Page 87 ASCII mode Command message Response message RTU mode Command message Response message...
Страница 110: ...FST 500 Manual Page 110 Chapter 5 Troubleshooting 5 1 Over Current OC...
Страница 111: ...FST 500 Manual Page 111 5 2 Ground Fault 5 3 Over Voltage OV...
Страница 112: ...FST 500 Manual Page 112 5 4 Low Voltage Lv...
Страница 113: ...FST 500 Manual Page 113 5 5 Over Heat OH1 5 6 Overload...
Страница 114: ...FST 500 Manual Page 114 5 7 Keypad Display is Abnormal 5 8 Phase Loss PHL...
Страница 115: ...FST 500 Manual Page 115 5 9 Motor cannot Run...
Страница 116: ...FST 500 Manual Page 116 5 10 Motor Speed cannot be Changed...
Страница 134: ...FST 500 Manual Page 134...
Страница 135: ...FST 500 Manual Page 135...
Страница 144: ...FST 500 Manual Page 144 EMI Filter RF022M21BA RF075M43BA EMI Filter 16TDT1W4S Used on 0 5 3 HP 230V Three Phase Models...
Страница 145: ...FST 500 Manual Page 145 EMI Filter 40TDS4W4B Used on 5 7 5 HP 230V Three Phase Models...