- Page 19 -
2.3 Main Circuit
2.3.1 Main Circuit Connection
******************************************************************************************************************
!
Mains power terminals (R/L1, S/L2, T/L3)
Connect these terminals (R/L1, S/L2, T/L3) via a non-fuse breaker or earth leakage breaker to
3-phase AC power (some models to 1-phase AC power) for circuit protection. It is unnecessary to
consider phase-sequence.
It is recommended to add a magnetic contactor (MC) in the power input wiring to cut off power
quickly and reduce malfunction when activating the protection function of AC motor drives. Both
ends of the MC should have an R-C surge absorber.
Please make sure to fasten the screw of the main circuit terminals to prevent sparks which is
made by the loose screws due to vibration.
Please use voltage and current within the regulation shown in Appendix A.
When using a GFCI (Ground Fault Circuit Interrupter), select a current sensor with sensitivity of
200mA, and not less than 0.1-second detection time to avoid nuisance tripping.
Do NOT run/stop AC motor drives by turning the power ON/OFF. Run/stop AC motor drives by
RUN/STOP command via control terminals or keypad. If you still need to run/stop AC drives by
turning power ON/OFF, it is recommended to do so only ONCE per hour.
Do NOT connect 3-phase models to a 1-phase power source.
Terminal Symbol
Explanation of Terminal Function
R/L1, S/L2, T/L3
AC line input terminals (three phase)
U/T1, V/T2, W/T3
Motor connections
B1
– B2
Connections for brake resistor (optional)
Earth Ground
Содержание FST-500 Series
Страница 8: ...FST 500 Manual Page 8 1 1 3 External Parts and Labels...
Страница 9: ...FST 500 Manual Page 9 1 1 4 Remove instructions...
Страница 17: ...FST 500 Manual Page 17...
Страница 22: ...FST 500 Manual Page 22 2 4 Control Terminal Wiring Factory Settings...
Страница 27: ...FST 500 Manual Page 27 3 1 2 How to Operate the Digital Keypad LC M02E...
Страница 28: ...FST 500 Manual Page 28 3 1 3 LC M02E Reference Table for the 7 segment LED Display of the Digital Keypad...
Страница 49: ...FST 500 Manual Page 49 Commonly used V F Setting 1 General Purpose...
Страница 87: ...FST 500 Manual Page 87 ASCII mode Command message Response message RTU mode Command message Response message...
Страница 110: ...FST 500 Manual Page 110 Chapter 5 Troubleshooting 5 1 Over Current OC...
Страница 111: ...FST 500 Manual Page 111 5 2 Ground Fault 5 3 Over Voltage OV...
Страница 112: ...FST 500 Manual Page 112 5 4 Low Voltage Lv...
Страница 113: ...FST 500 Manual Page 113 5 5 Over Heat OH1 5 6 Overload...
Страница 114: ...FST 500 Manual Page 114 5 7 Keypad Display is Abnormal 5 8 Phase Loss PHL...
Страница 115: ...FST 500 Manual Page 115 5 9 Motor cannot Run...
Страница 116: ...FST 500 Manual Page 116 5 10 Motor Speed cannot be Changed...
Страница 134: ...FST 500 Manual Page 134...
Страница 135: ...FST 500 Manual Page 135...
Страница 144: ...FST 500 Manual Page 144 EMI Filter RF022M21BA RF075M43BA EMI Filter 16TDT1W4S Used on 0 5 3 HP 230V Three Phase Models...
Страница 145: ...FST 500 Manual Page 145 EMI Filter 40TDS4W4B Used on 5 7 5 HP 230V Three Phase Models...