FST 500 Manual
- Page 82 -
Pr.80 Identity Code of the AC Motor Drive
Settings Read Only Factory Setting: ##
★
This parameter displays the identity code of the AC motor drive. The capacity, rated current, rated
voltage and the max. carrier frequency relate to the identity code. Users can use the following
table to check how the rated current, rated voltage and max. carrier frequency of the AC motor
drive correspond to the identity code.
115V series
230V series
kW
0.2
0.4
0.75
0.4
0.75
1.5
2.2
3.7
5.5
HP
0.25
0.5
1.0
0.5
1
2
3
5
7.5
Model Number(Pr.80)
20
22
24
00
02
04
06
08
10
Rated Output Current (A)
1.6
2.5
4.2
2.5
5.0
7.0
10
17
25
Max. Carrier Frequency(kHz)
15kHz
460V series
575V series
kW
0.75 1.5 2.2 3.7 5.5 7.5 0.75 1.5 2.2 3.7 5.5
7.5
HP
1
2
3
5
7.5
10
1
2
3
5
7.5
10
Model Number (Pr.80)
03
05
07
09
11
13
50
51
52
53
54
55
Rated Output Current (A)
3.0
4.0 5.0 8.2
13
18
1.7
3.0 4.2 6.6 9.9 12.2
Max. Carrier Frequency (kHz)
15kHz
10kHz
Pr.81 Time Duration of 1st Step Speed (correspond to Pr.17) Unit: 1 sec
Pr.82 Time Duration of 2nd Step Speed (correspond to Pr.18) Unit: 1 sec
Pr.83 Time Duration of 3rd Step Speed (correspond to Pr.19) Unit: 1 sec
Pr.84 Time Duration of 4th Step Speed (correspond to Pr.20) Unit: 1 sec
Pr.85 Time Duration of 5th Step Speed (correspond to Pr.21) Unit: 1 sec
Pr.86 Time Duration of 6th Step Speed (correspond to Pr.22) Unit: 1 sec
Pr.87 Time Duration of 7th Step Speed (correspond to Pr.23) Unit: 1 sec
Settings 00 to 9999 second Factory Setting: 00
◆
Pr.81 to Pr.87 input the duration of each Multi-step speed operation defined by Pr.17 to Pr.23.
Note:
If any duration is set to “0” (sec), the corresponding step operation will be skipped. This is
commonly used to reduce the number of program steps.
Pr.88 Communication Address
Settings 01 to 254 Factory Setting: 01
◆
This parameter sets the Ac drive address identification when using the RS-485 serial port for
communication.
Содержание FST-500 Series
Страница 8: ...FST 500 Manual Page 8 1 1 3 External Parts and Labels...
Страница 9: ...FST 500 Manual Page 9 1 1 4 Remove instructions...
Страница 17: ...FST 500 Manual Page 17...
Страница 22: ...FST 500 Manual Page 22 2 4 Control Terminal Wiring Factory Settings...
Страница 27: ...FST 500 Manual Page 27 3 1 2 How to Operate the Digital Keypad LC M02E...
Страница 28: ...FST 500 Manual Page 28 3 1 3 LC M02E Reference Table for the 7 segment LED Display of the Digital Keypad...
Страница 49: ...FST 500 Manual Page 49 Commonly used V F Setting 1 General Purpose...
Страница 87: ...FST 500 Manual Page 87 ASCII mode Command message Response message RTU mode Command message Response message...
Страница 110: ...FST 500 Manual Page 110 Chapter 5 Troubleshooting 5 1 Over Current OC...
Страница 111: ...FST 500 Manual Page 111 5 2 Ground Fault 5 3 Over Voltage OV...
Страница 112: ...FST 500 Manual Page 112 5 4 Low Voltage Lv...
Страница 113: ...FST 500 Manual Page 113 5 5 Over Heat OH1 5 6 Overload...
Страница 114: ...FST 500 Manual Page 114 5 7 Keypad Display is Abnormal 5 8 Phase Loss PHL...
Страница 115: ...FST 500 Manual Page 115 5 9 Motor cannot Run...
Страница 116: ...FST 500 Manual Page 116 5 10 Motor Speed cannot be Changed...
Страница 134: ...FST 500 Manual Page 134...
Страница 135: ...FST 500 Manual Page 135...
Страница 144: ...FST 500 Manual Page 144 EMI Filter RF022M21BA RF075M43BA EMI Filter 16TDT1W4S Used on 0 5 3 HP 230V Three Phase Models...
Страница 145: ...FST 500 Manual Page 145 EMI Filter 40TDS4W4B Used on 5 7 5 HP 230V Three Phase Models...