AD-4401A Page
22
●
Correction flow
When the judgment result after the feeding process is underweight, the following is automatically performed
up to the maximum number of correction flow (Sq F-08) to compensate for the underweight value.
1. When the weight value is judged to be underweight, the small flow output turns ON.
2. When the correction flow ON time (Sq F-16) has passed, the small flow output turns OFF.
3. When the correction flow OFF time (Sq F-17) has passed and the weight value is stable (Sq F-07), the
weight value is judged.
Timing chart
Final weight
Free fall
Judgment: Overweight
Judgment: Underweight
Judgment: OK
Small flow output
Weighing end output
OK/Over/Under output
T5
T9
T10
T10
T9
Under
Over
Judge
Judge
Judge
T5: Judging delay time
T9: Correction flow ON time
T10: Correction flow OFF time