
Page 19
AD-4401A
●
Correction flow
When the judgment result after the feeding process is underweight, the following is automatically performed
up to the maximum number of correction flow (Sq F-08) to compensate for the underweight value.
1. When the weight value is judged to be underweight, the small flow output turns ON.
2. When the correction flow ON time (Sq F-16) has passed, the small flow output turns OFF.
3. When the correction flow OFF time (Sq F-17) has passed and the weight value is stable (Sq F-07), the
weight value is judged.
Timing chart
Final weight
Free fall
Judgment: Overweight
Judgment: Underweight
Judgment: OK
Small flow output
Weighing end output
OK/Over/Under Output
T5
T9
T10
T10
T9
Overweight
Underweight
T5: Judging delay time
T9: Correction flow ON time
T10: Correction flow OFF time
Judge
Judge
Judge
Содержание AD-4401A
Страница 1: ...AD 4401A Weighing Indicator INSTRUCTION MANUAL 1WMPD4003050 ...
Страница 64: ...AD 4401A Page 62 Save Cancel Input a setting value Select an item Normal mode ...
Страница 83: ...13 ...