4 - 13
Fixed Spot Thermometers
User Guide
SPOT Actuator
Address
Name
Read/ Write
Default
Values
Description
1
Firm
w
are V
ersion
r
Version
number
of
current
actuator
firm
w
are
2
ErrorCode
r
0x01
=
flash
write
error;
0x02
=
flash
read
error;
0x04
=
serv
o
ov
ercurrent error; 0x08 r
ange restricted
3
LimitStartP
osition
r
Position of
limit switches
denote
the
maximum
possible scan
range
4
LimitEndP
osition
r
5
PyroCurrentT
emp
r
Current temper
ature measured b
y the SPO
T thermometer
6
CurrentP
osition
r
Current position of the actuator
7
HotSpotP
osition
r
Unless the ‘billet scan’ option is set, at the end of a scan, the data
is
analysed
to
find
the
hotspot
position
-
the
centre
of
the
hottest
hot spot. This register is updated and the actuator mo
ved to that
position.
8
ScanMinT
emp
r
The minimum v
alue of the most recent scan
9
ScanMaxT
emp
r
The maximum v
alue of the most recent scan
10
DHCP
rw
0 = set IP; 1 = DHCP
11,12
SubnetMask
rw
255.255.0.0
Network
configur
ation
par
ameters
13,14
Current IP
Address[2]
r
15,16
SetIP
Address[2]
rw
10.1.10.60
17,18
Gatew
ayAddress[2]
rw
10.1.10.1
19-21
MAC Address[3]
r
00-0f
-88-81-
??-??
22
Tempat4mA
rw
200
These registers must be set to match the settings on the SPO
T
thermometer I/O menu, in either C or F
. Here they are set to
match the defaults for the AL EQS in degrees C
23
TempA
t20mA
rw
700
24
SetP
osition
rw
600
Change this register to force the actuator to mo
ve to the new
value.