SD4840EK User Manual
ADVANCED MICRO CONTROLS INC.
58
Current Loop Gain (continued)
Determining Current Loop Gain (optional)
Determining the current loop gain setting require the following system setup:
Stable line voltage at the correct level. (Don’t determine the setting at 24 Vdc when the drive will oper-
ate at 48 Vdc.)
Motor current set to the operating level. (Don’t determine the setting with a motor current of 2 amps if
the motor will operate at 3 amps in the production environment.)
Idle current reduction set to 100%, which means no reduction. (This setting should be used regardless
of the setting used in the production environment.)
An acoustically quiet environment. (You will be listening for quiet changes in the sound of the motor
when it is idle.)
1) Write a Current Loop Gain value of 5 to the SD4840EK.
2) Enable the SD4840EK and listen for a sound from the motor. It will subjectively sound like an AM radio
static.
3) If you don’t hear the radio static sound from the motor, repeat steps 1 and 2 with an increased Current Loop
Gain.
4) Once you hear the radio static sound from the motor, decrease the Current Loop Gain setting by 10% to
20%. The goal is to eliminate the sound from the motor.
Refer to the documentation for your programming software to learn how to set the Current
Loop Gain using the CoE registers and how to make the changes permanent. You can refer to
step 3.2.3,
of this manual for brief instructions when
using the TwinCAT software.
Notes on Other Configuration Words
Changes to the Idle Current only take effect at
the end of the first move after re-configuration.
The motor current can be set to any value within its range.
Invalid Configurations
The following configurations are invalid:
1) Setting any of the reserved bits in the configuration words.
2) Setting any parameter to a value outside of its valid range.
3) Configuring two or more inputs to have the same function, such as two CW Limit Switches. (An
error does not occur if two or more are configured as General Purpose Inputs.)
4) Setting the Input Configuration bits for any input to “111”. See table R5.2 on page 54 for more
information.
5) Using an encoder and not setting the Encoder_Resolution register (8010:06) to a valid value.
6) Setting the Stall Detection Enable Bit without configuring the SD4840EK to use the encoder.
7) Setting the Home to Encoder Z-Pulse Bit without configuring the SD4840EK to use the encoder.
Содержание SD4840EK
Страница 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0S310...
Страница 6: ...TABLE OF CONTENTS SD4840EK User Manual ADVANCED MICRO CONTROLS INC 6 Notes...
Страница 38: ...MOVE PROFILES SD4840EK User Manual ADVANCED MICRO CONTROLS INC 38 Notes...
Страница 48: ...CALCULATING MOVE PROFILES SD4840EK User Manual ADVANCED MICRO CONTROLS INC 48 Notes...
Страница 78: ...COMMAND DATA FORMAT SD4840EK User Manual ADVANCED MICRO CONTROLS INC 78 Notes...
Страница 94: ...INSTALLING THE SD4840EK SD4840EK User Manual ADVANCED MICRO CONTROLS INC 94 Notes...
Страница 104: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...